2008-10-31 15:17:06PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-2 SCOPE OF WORK (RESTROOMS): CLEARLY
 INDICATE IN THE SCOPE OF WORK THE ADDITION OF ONE
 LAVATORY SINK IN THE WOMENS BATHROOM FOR THE 7TH FLOOR
 AND ALSO PROVIDE SANITARY AND POTABLE WATER RISER
 DIAGRAMS FOR THE PROPOSED LAVATORY. PER FBC-2004
 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.3.5.1.3
 PLUMBING (3)(4)(13).
  
 2. SHEET A-3 SCOPE OF WORK (RESTROOMS): CLEARLY
 INDICATE IN THE SCOPE OF WORK THE ADDITION OF ONE
 LAVATORY SINK IN THE WOMENS BATHROOM FOR THE 9TH FLOOR
 AND ALSO PROVIDE A SANITARY AND POTABLE WATER RISER
 DIAGRAM FOR THE PROPOSED LAVATORY. PER FBC-2004 CHAPTER
 1, (W.P.B. AS AMENDED) SECTION 106.3.5.1.3 PLUMBING
 (3)(4)(13).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]