2008-10-28 12:03:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE STATE ON MECHANICAL PLAN HOW THE BATHROOM
 EXHAUST FANS ARE BEING CONTROLLED TO PREVENT THE A/C
 SUPPLY AIR FROM ENTERING THE SPACE WHEN THE EXHAUST
 FANS ARE NOT RUNNING AND BEING RETURNED TO THE A/C
 SYSTEM THROUGH THE MAKE-UP TRANSFER DUCT, SEE 2004
 FBC/M 403.2.1 (3) AND 407.1.
  