| Plan Review Notes For Permit 08100489 |
| Permit Number |
08100489 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-28 12:03:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) PLEASE STATE ON MECHANICAL PLAN HOW THE BATHROOM | | | EXHAUST FANS ARE BEING CONTROLLED TO PREVENT THE A/C | | | SUPPLY AIR FROM ENTERING THE SPACE WHEN THE EXHAUST | | | FANS ARE NOT RUNNING AND BEING RETURNED TO THE A/C | | | SYSTEM THROUGH THE MAKE-UP TRANSFER DUCT, SEE 2004 | | | FBC/M 403.2.1 (3) AND 407.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|