Plan Review Notes
Plan Review Notes For Permit 08100484
Permit Number 08100484
Review Stop P
Sequence Number 3
Notes
Date Text
2009-04-01 08:49:38REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMIING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT SK-1 SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. PLEASE CORRECT THE FOLLOWING:
  
 A. THE FLOOR SINK REQUIRES A TRAP. SECTION 1002.1.
  
 B. THE WATER CLOSET ON THE FIRST FLOOR IS NOT VENTED.
 SECTION 908.3. WHERE THE FIXTURE DRAINS CONNECT AT
 DIFFERENT LEVELS, THE UPPER FIXTURE SHALL NOT BE A
 WATER CLOSET.
  
 C. THERE ARE CONFLICTING NOTES. ONE NOTE STATES "NEW
 HWH RELIEF VALVE & NEW WASHER TO TIE INTO EXISTING
 JANITOR'S SINK DRAIN", BUT ANOTHER NOTE INDICATES "NEW
 WASHER CONNECTION BOX WITH ARRESTORS. ALSO NO JANITOR
 SINK IS SHOWN ON THE RISER DIAGRAM. PLEASE CLARIFY.
 SECTION 106.1.1. IF THERE IS NO JANITOR SINK, THEN
 PLEASE INDICATE WHERE THE RELIEF VALVE DISCHARGE
 TERMINATES. SECTION 504.6.1.
  
 2. THE TITLE BLOCK IS REQUIRED TO NAME OR IDENTIFY THE
 PROJECT PER FAC 61G1-16.004(3) & FS 481.2055. PLEASE
 SHOW COMPLIANCE WITH NAME OF PROJECT OR ADDRESS ETC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved