| Plan Review Notes For Permit 08100484 |
| Permit Number |
08100484 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-08 11:29:28 | | | | | | | | | | PASSED/PROVISO -- REVISION REQUIRED | | | | | | SHT P.1 SANITARY RISER DIAGRAM. THE COMBINATION DRAIN | | | AND VENT SYSTEM, (FOR THE PEDICURE DRAINS), SHALL BE | | | PROVIDED WITH A DRY VENT CONNECTED AT ANY POINT WITHIN | | | THE SYSTEM. A DRY VENT CAN BE INSTALLED IN THE WALL TO | | | THE EAST SIDE OF THE DRAINS TO COMPLY. (SEE RED LINE | | | MARK UP ON PLANS). SECTION 912.2.2. | | | | | | SHT P.1 POTABLE WATER ISOMETRIC RISER DIAGRAM. WATER | | | HAMMER ARRESTORS ARE REQUIRED AT THE WASH MACHINE WATER | | | SUPPLIES. SECTION 604.9. ARRESTORS SHALL BE INSTALLED | | | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" PER PDI-WH | | | 201. | | | | | | | | | | | | | | | . |
|