Plan Review Notes
Plan Review Notes For Permit 08100484
Permit Number 08100484
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-31 16:58:56PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.1 PROPOSED GROUND FLOOR PLAN: PLEASE KNOW
 THAT FOR A BUSSINESS OCCUPANCY THE INDICATED NEW WATER
 COOLER IS UNACCEPTABLE. A DRINKING FOUNTAIN IS REQUIRED
 FOR A BUSSINESS OCCUPANCY PER FBC-2004 PLUMBING TABLE
 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES.
 PLEASE KNOW THAT THE DRINKING FOUNTAIN IS REQUIRED TO
 BE ACCESSIBLE AND COMPLIANT WITH THE FOLLOWING FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **SECTION 11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 SECTION 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO
 OUTLET MAXIMUM.
  
 SECTION 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER
 FLOW IN TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL
 TO FRONT OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON
 AN ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS
 WITHIN 3" OF THE FRONT OF FOUNTAIN.
  
 SECTION 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR FRONT EDGE.
  
 SECTION 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X
 48" FLOOR SPACE.
  
 SECTION 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING
 FOUNTAIN IS PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS
 WHO USE WHEELCHAIRS IN ACCORDANCE WITH SECTION 11-4.15
 AND ONE ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING
 OR STOOPING.(THIS CAN BE ACCOMMODATED BY THE USE OF A
 HI-LO FOUNTAIN OR BY SUCH OTHER MEANS AS WOULD ACHIEVE
 THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON EACH
 FLOOR).
  
 2. SHEET A.1 PROPOSED GROUND FLOOR PLAN: THE FLOOR IS
 INDICATING A NEW LAVATORY BEING INSTALLED IN A NEW
 LOCATION. PLEASE PROVIDE THE FOLLOWING REQUIRED
 INFORMATION PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS THAT ARE MISSING FROM SHEET
 A.4 DETAIL 2B, TOILET ROOM INTERIOR ELEVATIONS. PLEASE
 CLEARLY INDICATE THE FOLLOWING.
  
 SECTION 11-4.19.2 HEIGHT AND CLEARANCES. 29" A.F.F. TO
 THE BOTTOM OF THE APRON. (SEE FIGURE 31 ATTACHED TO
 THESE COMMENTS) KNEE CLEARANCE 8" MIN. DEPTH 17" MIN.
 TOE CLEARANCE 6" MAX OUT FROM WALL MIN 9" A.F.F.
  
 3. SHEET A.1 PROPOSED GROUND FLOOR PLAN INDICATES A
 VESSEL SINK, FAUCET & CABINET. PLEASE CLARIFY THE
 INTENT OF THIS SINK. IS THE SINK WORK RELATED? IF NOT
 THE FOLLOWING IS REQUIRED FOR THE SINK PER THE FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 4. SHEET A.1 PROPOSED MEZZANINE PLAN IS INDICATING A
 NEW FIBERGLASS SHOWER UNIT. PLEASE KNOW THAT THE SHOWER
 SHALL BE COMPLIANT WITH THE FOLLOWING FBC-2004 CHAPTER
 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37)
 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37)
 11-4.21.7 CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB
 REQUIRED IN MINIMUM 30" X 60" STALLS)
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3.
 PLUMBING (4)(6)(13): PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS OF PROPOSED
 FIXTURES.
  
 6. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS (IF APPLICABLE) WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]