Plan Review Notes
Plan Review Notes For Permit 08100484
Permit Number 08100484
Review Stop M
Sequence Number 1
Notes
Date Text
2008-10-28 16:01:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE
 DOOR TO THE EXTERIOR CORRIDOR, PER 2004 FBC/M 501.2
 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS AT A POINT
 WHERE IT WILL NOT CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM. THE DRYER EXHAUST WOULD BE A NUISANCE IF
 DISCHARGED IN TO THE EXTERIOR CORRIDOR AND MAY GET BACK
 INTO THE VENTILATION SYSTEM WHEN THE DOOR IS OPENED.
 PLEASE CORRECT.
  
 2) PLEASE SHOW ON MECHANICAL PLAN THE CFM'S FOR EXHAUST
 FAN BROAN L300L, SEE 2004 FBC/M 403.2.
  
 3) PLEASE SHOW ON MECH. PLAN THE CFM'S FOR THE BATHROOM
 EXHAUST FANS, SEE 2004 FBC/M 403.2.
  
 4) SHOW ON MECH. PLAN THAT ONE OF THE NEW EXHAUST FANS
 IS TO EXHAUST THE SHOWER ROOM, SEE 2004 FBC/M TABLE
 403.3.
  
 5) STATE ON MECH. PLAN THE MINIMUM SIZE THE EXISTING
 EXHAUST DUCT GOING TO THE ROOF CAN BE FOR THE THREE NEW
 EXHAUST FANS TO TIE INTO, OR DO YOU WANT THEM EACH TO
 BE DUCTED DIRECTLY TO THE ROOF VENT ON THE ROOF, SEE
 2004 FBC/M 603.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]