| 2008-11-04 08:06:23 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: TITLE BLOCKS FOR ARCHITECT IS MISSING THE |
| | PRINTED NAME AND PRINTED LICENSE NUMBER OF SAID |
| | DESIGNER. |
| | FAC 61G1-16.004. |
| | |
| | 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| | PLEASE NOTE SECTION FOR TRACK LIGHTING. PLEASE ALSO |
| | KNOW BEFORE ANY NEW FIXTURES MAY BE INSTALLED THE |
| | EXISTING LIGHTING LEVELS NEED TO BE DETERMINED BEFORE |
| | ANY NEW MAY BE INSTALLED. |
| | THE FIXTURE LEGEND NEEDS TO BE COMPLETED AT THIS TIME |
| | WITH PRE-DETERMINED FIXTURES SO THAT CODE COMPLIANCE |
| | MAY BE VERIFIED. THE LIGHTING FIXTURES MAY ALWAYS BE |
| | REVISED AT A LATER DATE. |
| | |
| | 3) NOTE: PLEASE INDICATE WHETHER OR NOT THE EXISTING |
| | STAIRS MEET THE MINIMUM FOR THE LIFE SAFETY CODE FOR |
| | LIGHTING LEVELS. PLEASE SEE NFPA-101 7.8.1.3 AS THE |
| | LEVELS SHALL MEET THE MINIMUM LEVELS FOR NORMAL USE AND |
| | THE MINIMUM UNDER EMERGENCY CONDITIONS. |
| | |
| | 4) NOTE: PLEASE VERIFY LOAD AND CIRCUITING FOR THE NEW |
| | PROPOSED TANK LESS WATER HEATER. THE LOAD SHOWN APPEARS |
| | TO BE VERY LOW HOWEVER THIS COMMENT IS FOR INFORMATION |
| | ONLY. IF THIS UNIT IS INDEED 4.5KVA THEN NO RESPONSE IS |
| | NEEDED. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS |
| | INDICATING THE LISTING OF A NRTL. (NATIONALLY |
| | RECOGNIZED TESTING LABORATORY. |
| | 110.3 |
| | |
| | 5) NOTE: PLEASE SEE REVISED 2005 NEC AS SECTION 408.4 |
| | REQUIRES ALL CIRCUITING TO BE SPECIFIC TO ROOMS AND |
| | AREAS IN WHICH THEY FEED. THE USE OF GENERAL LIGHTING |
| | OR GENERAL RECEPTACLES IS NO LONGER PERMITTED. THESE |
| | NEE TO BE SPECIFIC TO ROOMS ARE AREAS WITH EITHER AND |
| | ALPHA OR NUMERIC DESIGNATION. |
| | FBC 106.1.1, 106.5. |
| | |
| | 6) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR A/C |
| | #2 NEEDS TO BE SIZED PER 424.3B. |
| | IF THIS IS THE HEAT LOAD WHICH IS SHOWN THE MINIMUM OCP |
| | IS REQUIRED TO BE SIZED AT 125%. |
| | PLEASE ADJUST. |
| | |
| | 7) NOTE: PLEASE BE SURE SHOW TRACK LOAD PER 220.43 |
| | |
| | 8) NOTE: PLEASE SEE 13-415.1.ABC.1.2, .1.3 FOR LIGHTING |
| | CONTROLS |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |