Plan Review Notes
Plan Review Notes For Permit 08100484
Permit Number 08100484
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-04 08:06:23 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: TITLE BLOCKS FOR ARCHITECT IS MISSING THE
 PRINTED NAME AND PRINTED LICENSE NUMBER OF SAID
 DESIGNER.
 FAC 61G1-16.004.
  
 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2.
 PLEASE NOTE SECTION FOR TRACK LIGHTING. PLEASE ALSO
 KNOW BEFORE ANY NEW FIXTURES MAY BE INSTALLED THE
 EXISTING LIGHTING LEVELS NEED TO BE DETERMINED BEFORE
 ANY NEW MAY BE INSTALLED.
 THE FIXTURE LEGEND NEEDS TO BE COMPLETED AT THIS TIME
 WITH PRE-DETERMINED FIXTURES SO THAT CODE COMPLIANCE
 MAY BE VERIFIED. THE LIGHTING FIXTURES MAY ALWAYS BE
 REVISED AT A LATER DATE.
  
 3) NOTE: PLEASE INDICATE WHETHER OR NOT THE EXISTING
 STAIRS MEET THE MINIMUM FOR THE LIFE SAFETY CODE FOR
 LIGHTING LEVELS. PLEASE SEE NFPA-101 7.8.1.3 AS THE
 LEVELS SHALL MEET THE MINIMUM LEVELS FOR NORMAL USE AND
 THE MINIMUM UNDER EMERGENCY CONDITIONS.
  
 4) NOTE: PLEASE VERIFY LOAD AND CIRCUITING FOR THE NEW
 PROPOSED TANK LESS WATER HEATER. THE LOAD SHOWN APPEARS
 TO BE VERY LOW HOWEVER THIS COMMENT IS FOR INFORMATION
 ONLY. IF THIS UNIT IS INDEED 4.5KVA THEN NO RESPONSE IS
 NEEDED.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS
 INDICATING THE LISTING OF A NRTL. (NATIONALLY
 RECOGNIZED TESTING LABORATORY.
 110.3
  
 5) NOTE: PLEASE SEE REVISED 2005 NEC AS SECTION 408.4
 REQUIRES ALL CIRCUITING TO BE SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED. THE USE OF GENERAL LIGHTING
 OR GENERAL RECEPTACLES IS NO LONGER PERMITTED. THESE
 NEE TO BE SPECIFIC TO ROOMS ARE AREAS WITH EITHER AND
 ALPHA OR NUMERIC DESIGNATION.
 FBC 106.1.1, 106.5.
  
 6) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR A/C
 #2 NEEDS TO BE SIZED PER 424.3B.
 IF THIS IS THE HEAT LOAD WHICH IS SHOWN THE MINIMUM OCP
 IS REQUIRED TO BE SIZED AT 125%.
 PLEASE ADJUST.
  
 7) NOTE: PLEASE BE SURE SHOW TRACK LOAD PER 220.43
  
 8) NOTE: PLEASE SEE 13-415.1.ABC.1.2, .1.3 FOR LIGHTING
 CONTROLS
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  