Plan Review Notes
Plan Review Notes For Permit 08100433
Permit Number 08100433
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-02-02 12:09:33*****DENIED****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADDRESSED:
  
 1. STAIRS SHALL COMPLY WITH THE REQUIREMENTS OF NFPA
 101, 2003, SEC. 7.2.2.
  
 2. PLEASE PROVIDE THE PRESCRIPTIVE STRENGTH REQUIREMENT
 OFR THE HANDRAILS AND GUARDRAILS.
  
 3. CLEARLY INDICATE IF THERE ARE ANY BUILDING OPENINGS
 BENEATH THE STAIRS AND PROVIDE DISTANCE INFORMATION.
  
 4. DRAWINGS DO NOT INDICATE HOW STAIRS ARE RELEVANT TO
 BUILDING OCCUPANTS WITH REGARDS TO MEANS OF EGRESS.
  
 5. OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722