| 2008-11-12 16:32:39 | EXTERIOR STAIRWAY BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- CLARIFY WHICH BUILDING IS THE CONSTRUCTION TAKEN |
| | PLACE. PERMIT APPLICATION AND ARCHITECTURAL PLANS CALL |
| | FOR 1017 N. OLIVE AVE, WHILE NOTICE OF COMMENCEMENT |
| | CALLS FOR 1021 N. OLIVE AVE. ALSO, ACCORDING TO |
| | PROPERTY APPRAISAL WEBSITE PARCEL ID # SHOWN ON PERMIT |
| | APPLICATION CORRESPONDS TO 1021 N. OLIVE AVE. |
| | |
| | 2- PROVIDE NOTICE OF COMMENCEMENT WITH CORRECT ADDRESS |
| | AND PARCEL ID NUMBER. |
| | |
| | 3- PROVIDE COMPLETE STAIRWAY FRAMING DETAILS DETAILS |
| | AND SECTIONS TO VERIFY COMPLIANCE WITH TABLE 1607.1 FBC |
| | 2004 AND SEC. 1609.1 FBC 2004 (NOTE: SPECIFY ALL LOADS |
| | TAKEN INTO CONSIDERATION FOR THE DESIGN). SHOW LOCATION |
| | OF STEEL COLUMNS AND WOOD COLUMNS. PROVIDE ANCHORING OF |
| | STAIRS AT BOTTOM. SPECIFY STRINGERS AND CONNECTIONS. |
| | SPECIFY ATTACHMENT OF TOP STAIR LANDING TO EXISTING |
| | BUILDING. PROVIDE COMPLETE DETAILS AND SIZE OF STEEL |
| | BUCKET TO FASTEN TO STEEL COLUMN. CLARIFY DETAIL |
| | CONNECTION AT TOP OF WOOD COLUMN. SPECIFY MATERIALS |
| | USED TO BUILD STAIRS. |
| | |
| | 4- PROVIDE GUARDRAIL AND HANDRAIL DETAILS/SECTIONS TO |
| | SHOW COMPLIANCE WITH STRUCTURAL DESIGN TABLE 1607.1 AND |
| | SEC. 11-4.26.3 OF FBC 2004. |
| | |
| | 5- PROVIDE RISER, TREAD AND NOSING DETAILS TO VERIFY |
| | COMPLIANCE WITH SEC. 11-4.9.2 AND 11-4.9.3 FBC 2004. |
| | ***NOTE: OPEN RISERS ARE NOT ALLOWED. |
| | |
| | 6- HANDRAILS NEED TO COMPLY WITH SEC. 11-4.9.4(2) AND |
| | FIGURE 19 OF CHAPTER 11 FBC 2004. |
| | ***NOTE: CHECK TOP AND BOTTOM HANDRAIL ENDING. |
| | |
| | 7- TYPICAL STAIR DETAILS DON'T APPLY TO THIS PROJECT. |
| | THEY ARE FOR STAIRS ATTACHED TO A WALL. REVISE SIZE OF |
| | HANDRAIL TO COMPLY WITH SEC. 11-4.26.2 FBC 2004. CHECK |
| | RISER AND TREAD SIZES. REVISE AS REQUIRED TO MATCH |
| | PROPOSED STAIRS. |
| | |
| | 8- PROVIDE DETAILS SHOWING COMPLIANCE WITH THE |
| | GUARDRAIL HEIGHT ( 42" AS REQUIRED BY SEC. 1012.2 FBC |
| | 2004) , AND OPENINGS LIMITATIONS, SEC 1012.3 FBC 2004. |
| | |
| | 9- PROVIDE DETAILS SPECS SHOWING COMPLIANCE WITH |
| | HANDRAIL HEIGHT AND OTHER REQUIREMENTS OF SEC. 11-4.9.4 |
| | FBC 2004. |
| | |
| | 10- PLANS NEED TO SPECIFY SPECIFIC CODES AND YEAR (SEC. |
| | 105.3 AND 105.3.1 OF CITY AMENDMENTS TO FBC 2004) AND |
| | ALL INFORMATION REQUIRED BY SEC. 1603 FBC 2004. |
| | NOTE: CITY OF WEST PALM BEACH IS LOCATED ON BASIC WIND |
| | SPEED OF 140MPH. SEC. 117 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- PROVIDE PLANS SHOWING EXISTING STAIRS AND LANDINGS |
| | TO BE REMOVED. CLARIFY WHY EXISTING LANDING TO BE |
| | REMOVED IS SHOWN LARGER THAN THE PROPOSED ONE. PROVIDE |
| | INFORMATION SHOWING BUILDING USE AND NUMBER OF PEOPLE |
| | TO VERIFY COMPLIANCE WITH MINIMUM REQUIRED WIDTH OF |
| | MEANS OF EGRESS OF SEC. 1009.1 FBC 2004. (44" MINIMUM |
| | UNLESS EXCEPTIONS APPLY). |
| | |
| | 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. UPDATE PERMIT VALUATION TO INCLUDE EXISTING STAIRS |
| | DEMOLITION AND DEBRIS REMOVAL, PROFESSIONAL DESIGNER |
| | FEES AND CONTRACTOR OVERHEAD AND PROFIT AS REQUIRED BY |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 13- SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. |
| | 301.5 OF 2004 FLORIDA EXISTING BUILDING CODE. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS. |
| | NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED TO |
| | PROVIDE COMPLETE REPORT. |
| | |
| | 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- SCALE FOR DRAWING DETAIL 4/SP IS INCORRECT. REVISE |
| | AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |