2009-08-06 15:07:30REVISED M1 AND M2 DENIED
  
 THIS REVISION HAS ELIMINATED TTHE DUCT SMOKE DETECTOR
 AS REQUIRED PER FBC-M 606.2.1. SUBMITTAL FORM CLAIMS
 THAT THE DESIGN CAPACITY OF THE NEW RTU DOES NOT EXCEED
 2000 CFM. HOWEVER, THE REVISED FLOOR PLAN A TOTAL AIR
 SUPPLY OF 2210 CFM. THE DUCT SMOKE DETECTOR SHALL NOT
 BE ELIMINATED. THE DUCT SMOKE DETECTOR SHALL BE
 INSTALLED AND CONNECTED TO THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH FBC-M 606.4.
  