| Plan Review Notes For Permit 08100428 |
| Permit Number |
08100428 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2009-08-06 15:07:30 | REVISED M1 AND M2 DENIED | | | | | | THIS REVISION HAS ELIMINATED TTHE DUCT SMOKE DETECTOR | | | AS REQUIRED PER FBC-M 606.2.1. SUBMITTAL FORM CLAIMS | | | THAT THE DESIGN CAPACITY OF THE NEW RTU DOES NOT EXCEED | | | 2000 CFM. HOWEVER, THE REVISED FLOOR PLAN A TOTAL AIR | | | SUPPLY OF 2210 CFM. THE DUCT SMOKE DETECTOR SHALL NOT | | | BE ELIMINATED. THE DUCT SMOKE DETECTOR SHALL BE | | | INSTALLED AND CONNECTED TO THE BUILDING FIRE ALARM | | | SYSTEM IN ACCORDANCE WITH FBC-M 606.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|