Plan Review Notes
Plan Review Notes For Permit 08100428
Permit Number 08100428
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-24 15:15:39 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved