| 2008-10-28 12:33:51 | BUILDING PLAN REVIEW |
| | PERMIT: 08100428 |
| | ADD: 1525 N. FLAGLER DR. #100 |
| | CONT: MORGAN CONTRACTING GROUP INC. |
| | TEL: (561)330-9600 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 10-28-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE INDICATED ON THE PLANS. |
| | |
| | 3) FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER |
| | CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. NOTE: |
| | PAINT ON DRYWALL IS NOT CONSIDERED A HARD SURFACE. |
| | |
| | 4) FBC 11-7.1(2) (I) A PORTION OF THE MAIN COUNTER |
| | SHALL HAVE A MINIMUM LENGTH OF 36 INCHES AND A MAXIMUM |
| | HEIGHT OF 36 INCHES. SHEET A3.1 #3 SHOWS THE RECEPTION |
| | DESK HEIGHT AT 3?- 6?. |
| | |
| | 5) SHEET A1.0 DOOR #3 CLEARANCE SHALL MEET THE |
| | REQUIREMENTS OF 11-4.13.6 MANEUVERING CLEARENCES AT |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. NOTE: 18? MINIMUM. |
| | |
| | |
| | |
| | 6) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. THE PLANS NEED TO |
| | CLEARLY SHOW THE EXISTING WALLS AND THE NEW WALLS. |
| | PROVIDE A WALL LEGEND TO SHOW THIS ASPECT OF THE PLANS. |
| | |
| | 7) ROOM 108 ON SHEET A1.0 WHERE THE DOOR IS REMOVED, IS |
| | THAT AN EXTERIOR WALL OR A PARTITION WALL WHICH NEEDS A |
| | FIRE RATING? IF THAT IS A PARTITION WALL, STATE THE UL |
| | NUMBER FOR THE NEW WALL. THERE IS NO WALL TYPE |
| | INDICATED. |
| | |
| | 8) SHOW THE FOLLOWING INFORMATION FOR THE BREAK ROOM |
| | SINK ON THE PLANS. FBC 11-4.24.2. SINKS SHALL BE |
| | MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" |
| | ABOVE THE FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT |
| | IS AT LEAST 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE |
| | PROVIDED UNDERNEATH SINKS. 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES UNDERNEATH THE SINK. |
| | |
| | 9) SHEET A1.0 ACCESSIBLE TOILET SHOWS TWO DIFFERENT |
| | TYPES OF WALL SYMBOLS IN BACK OF THE WATER CLOSET. WILL |
| | THERE BE A TYPE P-1 AND A TYPE P-2 WALL CONSTRUCTED IN |
| | THIS AREA? STATE HOW THE TOP AND BOTTOM TRACK WILL BE |
| | FASTENED TO THE STRUCTURE. CLARIFY. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |
| | |
| | |