| 2008-11-22 10:59:05 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. SCOPE OF WORK STATES "ADDING AIR RUN - HYDROGEN |
| | PUMP..." IS THERE AN AIR LINE OR HYDROGEN LINE BEING |
| | INSTALLED? SCOPE INDICATES AIR LINE BUT PLANS CALL FOR |
| | HYDROGEN LINE. PLANS DO NOT SHOW HYDROGEN PUMP, ONLY |
| | AIR PUMP AND AIR COMPRESOR. PLEASE CLARIFY SCOPE ON |
| | PERMIT DESCRIPTION AND ON PLANS. |
| | |
| | 2. NO INFORMATION WAS PROVIDED REGARDING THE |
| | EQUIPMENT/APPLIANCES BEING INSTALLED. PROVIDE SUBMITTAL |
| | DATA FOR EACH PIECE OF EQUIPMENT/APPLIANCE BEING |
| | INSTALLED WITH LISTING INFORMATION. ALL APPLIANCES |
| | REGULATED BY THIS CODE SHALL BE LISTED AND LABELED IN |
| | ACCORDANCE WITH FBCM 301.4. |
| | |
| | 3. IS THIS NEW EQUIPMENT BING INSTALLED OUTDOORS? NO |
| | INFORMATION WAS PROVIDED REGARDING WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING PER FBCM 301.13. SEE FBCB 1609 |
| | FOR WIND RESISTANCE REQUIREMENTS. ALSO, APPLIANCES |
| | INSTALLED IN OTHER THAN INDOOR LOCATIONS SHALL BE |
| | LISTED AND LABELED FOR OUTDOOR INSTALLATION IN |
| | ACCORDANCE WITH FBCM 303.6. |
| | |
| | 4. IF AIR AND/OR HYDROGEN LINES ARE BEING INSTALLED, |
| | THIS WORK IS OUT OF THE SCOPE OF GC LICENSE. PROPERLY |
| | LICENSED CONTRACTORS SHALL SIGN ON TO PERMIT |
| | APPLICATION OR PROVIDE SEPARATE APPLICATION(S) PRIOR TO |
| | ISSUANCE IN ACCORDANCE WIT F.S. 489.105(3). SEPARATE |
| | ELECTICAL AND LOW VOLTAGE PERMITS ALSO REQUIRED FOR |
| | POWER AND CONTROL/MONITORING WIRING RELATED TO THIS |
| | WORK. |
| | |