| Plan Review Notes For Permit 08100427 |
| Permit Number |
08100427 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-13 14:57:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | | | | | | | 1. DECLARE AN OCCUPANCY CLASSIFICATION. PURPOSE OF THIS | | | PUMP AND LINE IS NOT CLEAR. | | | | | | 2. THE DRAWING IS LABELED BOTH CROSS SECTION AND PLAN | | | VIEW, BUT SEEMS TO BE ONE DRAWING WHICH IS A | | | COMBINATION OF THREE SEPARATE DETAILS. PLEASE PROVIDE | | | THESE DETAILS WITH ENOUGH SEPARATION BETWEEN THEM SO | | | THAT THEY ARE UNDERSTANDABLE; CROSS SECTIONS SHOULD | | | HAVE A REFERENCE ON THE (FLOOR) PLAN TO SHOW HOW THEY | | | ARE RELATED. SCOPE OF WORK NOT CLEAR. | | | | | | 3. WHO WILL BE PERFORMING THE INSTALLATION OF AIR RUN | | | AND HYDROGEN PUMP? HAVE THIS CONTRACTOR SIGN ON AS A | | | SUBCONTRACTOR. | | | | | | 4. SCOPE OF WORK NOT CLEAR. APPLICATION STATES "ADDING | | | AN AIR RUN - HYDROGEN PUMP TO EXISTING SYSTEM". IS A | | | NEW PUMP BEING INSTALLED? PROVIDE ANCHORING DETAIL TO | | | SHOW HOW THIS WILL RESIST WIND LOADS, FBC1609. | | | | | | | | | |
|