| Date |
Text |
| 2008-10-30 13:28:41 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| | CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION 106.5 |
| | RECORD RETENTION. |
| | THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| | 2007 REVISIONS". |
| | |
| | 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | 3. THE ADDRESS IS INCOMPLETE ON ALL PLAN SHEETS. THE |
| | SUITE NUMBER 110 IS MISSING FROM THE ADDRESS. PLEASE |
| | CORRECT PER FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED |
| | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | AND SECTION 106.5 RECORD RETENTION. |
| | |
| | 4. SHEET A2 INTERIOR ELEVATION DETAIL (9) @ LOUNGE: |
| | PLEASE CORRECT/ADD THE FOLLOWING REQUIRED INFORMATION |
| | PER THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| | SECTION TO THE DETAIL FOR THE ACCESSIBLE SINK. |
| | |
| | *SECTION 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR |
| | COUNTER. (DETAIL INCORRECTLY INDICATES 3'-0") |
| | |
| | *SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, |
| | 30" WIDE, AND 19" DEEP. (OPEN FRONT REQUIRED, REMOVE |
| | CABINET DOORS @ SINK) |
| | |
| | *SECTION 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| | |
| | 5. SHEET A4 DETAILS: PLEASE ADD THE FOLLOWING REQUIRED |
| | INFORMATION PER THE FBC-2004 CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE SECTIONS FOR THE FOLLOWING |
| | ACCESSIBLE PLUMBING FIXTURES. |
| | |
| | *DRINKING FOUNTAIN SECTION 11-4.15. |
| | |
| | SECTION 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR |
| | SIDE MOUNTED NEAR FRONT EDGE. |
| | |
| | SECTION 11-4.15.5 CLEARANCES. KNEE 27" HIGH. |
| | |
| | *WATER CLOSET SECTION 11-4.16. |
| | |
| | SECTION 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE |
| | MAX. 44" HIGH. |
| | |
| | 6. SHEET P-1 DETAIL (2) SANITARY PLUMBING ISOMETRIC |
| | DIAGRAM: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004 |
| | PLUMBING CODE SECTIONS. |
| | |
| | A} W.C. #2 DOES NOT REFLECT THE FLOOR PLAN OF SHEET A1. |
| | PLEASE KNOW THAT THERE ARE TWO LAVATORIES BEING |
| | INDICATED IN THE ISOMETRIC, HOWEVER THE FLOOR PLAN IS |
| | ONLY INDICATING ONE LAVATORY. PLEASE CORRECT PER |
| | SECTION 401.1 AND 701.1 SCOPE. |
| | |
| | B} EXAM ROOM #4 AND #5 CLEARLY INDICATE THE FIXTURE |
| | TYPE ON THE ISOMETRIC. PER SECTION 401.1 AND 701.1 |
| | SCOPE. |
| | |
| | C} PLEASE KNOW THAT THE LABORATORY SINK PLUMBING ON |
| | BOTH THE SANITARY PLUMBING PLAN AND THE SANITARY |
| | PLUMBING ISOMETRIC DIAGRAM IS BEING INDICATED IN THE |
| | WRONG LOCATION AND DOES NOT REFLECT THE FLOOR PLAN OF |
| | SHEET A1. PLEASE CORRECT PER SECTION 701.1 SCOPE. |
| | |
| | 7. SHEET P-2 DETAIL (2) WATER PLUMBING ISOMETRIC |
| | DIAGRAM: PLEASE CLEARLY INDICATE THE REQUIRED FULL-OPEN |
| | VALVE LOCATED ON THE WATER SUPPLY PIPE TO THE WATER |
| | HEATER. PER FBC-2004 PLUMBING SECTION 606.1 LOCATION OF |
| | FULL-OPEN VALVES (7). |
| | |
| | 8. THE WATER HEATER AND HOT WATER PIPE INSULATION ARE |
| | MISSING FROM THE ENERGY CALCULATIONS. PER FBC-2004 |
| | CHAPTER 13, TABLE 13-411.1.ABC.2 MINIMUM PIPE |
| | INSULATION AND TABLE 13-412.1.ABC.3 PERFORMANCE |
| | REQUIREMENTS FOR WATER HEATING EQUIPMENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |