| 2008-10-23 10:14:59 | |
| | 10-23-08 |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08100422 |
| | ADD: 3109 45TH STREET #100 |
| | CONT: VILLA FRANCA DESIGN |
| | TEL: (561)575-2288 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| | SHALL BE SHOWN ON THE PLANS. |
| | |
| | 4) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUBMIT AN EXISTING |
| | FLOOR PLAN OF THE AREA PRIOR TO THE BATHROOM |
| | INSTALLATION. |
| | |
| | 5) THE DESCRIPTION ON THE APPLICATION STATES ?RELOCATE |
| | INTERIOR BATHROOMS? SHOW ON THE DRAWINGS WHERE THE |
| | EXISTING BATHROOMS ARE AND WHERE THEY WILL BE RELOCATED |
| | TO. |
| | |
| | 6) SHEET A1 SHOWS THE BATHROOM DOORS SWINGING OUT AND |
| | SHEET M-P-1 SHOWS THEM SWINGING IN. THE FLOOR PLAN ON |
| | EACH SHEET SHALL MATCH EACH OTHER. NOTE: FBC 11-4.22.2 |
| | ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH |
| | SECTION 11-4.13. DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | |
| | 7) THE FINISH SCHEDULE ON SHEET A1 FAILS TO INDICATE |
| | THE WALL FINISHES IN THE BATHROOMS. NOTE: FBC 1202.2 |
| | WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| | OF 4 FEET ABOVE THE FLOOR. PLEASE PROVIDE ADDITIONAL |
| | INFORMATION. |
| | |
| | 8) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. INDICATE THE LEVEL ON THE DRAWINGS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |