| Plan Review Notes For Permit 08100397 |
| Permit Number |
08100397 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-29 11:20:34 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 2) PLEASE CORRELATE THE ADDRESS ON PLANS TO MATCH THE | | | PERMIT APPLICATION. | | | | | | 3) THE TERM SMOKE DETECTOR WOULD SUGGEST THAT THE | | | DEVICES ARE TIED INTO THE BUILDING FIRE ALARM SYSTEM | | | THAT WOULD INITIATE A GENERAL FIRE ALARM. DEVICES | | | LOCATED IN THE LIVING UNITS THAT ARE RESPONSIVE TO | | | SMOKE WOULD BE SMOKE ALARMS. PLEASE MAKE CORRECTION TO | | | PLANS WHERE APPLICABLE. | | | | | | 4) WILL WORK IMPACT THE FIRE SPRINKLER SYSTEM? SEPARATE | | | SHOP DRAWINGS AND PERMITS MAY BE REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|