 APPLICATION #08100397 ELECTRICAL PLAN REVIEW
 717 S OLIVE AVENUE 10/29/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ADDRESS ON THE APPLICATION IS CORRECT BUT DOES
 NOT CORRELATE WITH THE ADDRESS ON THE PLANS.
  
 2} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 3} IT APPEARS THAT THE TUB IN THE MASTER BATH HAS BEEN
 REPLACED OR REFITTED WITH A RECIRCULATION PUMP.
 INDICATE COMPLIANCE WITH ARTICLE 680 VII.
  
 4} THE RECEPTACLE IN THE MASTER BATH LOCATED IN THE
 KNEE SPACE IS INDICATED AS NEW PER THE LEGEND, AND DOES
 NOT MEET THE SPACING REQUIREMENT OF 215.52(D).
  
 4} INDICATE THE TYPE OF LUMINAIRES AND THE WATTAGES OF
 SAME, BEING INSTALLED UNDER THIS PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  