| 2008-10-28 12:00:23 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 INDICATES AN EXISTING WELL HEAD LOCATED |
| | INSIDE THE PROPOSE DETACHED GARAGE. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION OF THE EXISTING WELL HEAD ON THE |
| | RESUBMITTED PLANS PER THE FBC-2004 PLUMBING CODE |
| | SETIONS. |
| | |
| | A} PLEASE CLARIFY THE USE OF THE EXISTING WELL HEAD. IS |
| | THE EXISTING WELL HEAD FOR POTABLE WATER OR IRRIGATION. |
| | PLEASE CLEARLY INDICATE THIS ON THE RESUBMITTAL. PER |
| | FBC-2004 PLUMBING SECTION 601.1 SCOPE. |
| | |
| | B} PLEASE CLARIFY IF THERE IS ALSO AN EXISTING PUMP FOR |
| | THE EXISTING WELL HEAD AND IF THERE IS CLEARLY INDICATE |
| | ON THE RESUBMITTAL ITS LOCATION. PER FBC-2004 PLUMBING |
| | SECTION 601.1 SCOPE. |
| | |
| | C} PLEASE PROVIDE A DETAIL OF THE EXISTING WELL HEAD |
| | AND ANY RELATED PIPING AND PUMP. CLEARLY INDICATE ON |
| | THE DETAIL IF THE EXISTING WELL AND ANY RELATED PIPING |
| | AND PUMP ARE LOCATED ABOVE OR BELOW THE FINNISH FLOOR |
| | ELEVATION OF THE PROPOSED DETACHED GARAGE. PER FBC-2004 |
| | PLUMBING SECTION 601.1 SCOPE. |
| | |
| | D} CLEARLY INDICATE THAT THE EXISTING WELL HEAD AND ANY |
| | RELATED PIPING AND PUMP WILL BE PROTECTED FROM PHYSICAL |
| | DAMAGE THAT MAY OCCUR FROM A VEHICLE (SUCH AS A |
| | BOLLARD). PLEASE PROVIDE A DETAIL OF HOW EXISTING WELL |
| | HEAD AND ANY RELATED PIPING AND PUMP WILL BE PROTECTED. |
| | PER FBC-2004 PLUMBING SECTION 305.9 PROTECTION OF |
| | COMPONENTS OF PLUMBING SYSTEMS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |