2008-10-27 09:26:56 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE
 BUILDING OR STRUCTURE.
 225.32 LOCATION
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS
 SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED.
  
 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING
 ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE
 WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.
  
 INDICATE COMPLIANCE WITH THESE ARTICLES BY PROVIDING A
 RISER DIAGRAM
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  