| 2008-10-27 09:26:56 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} 225.31 DISCONNECTING MEANS |
| | MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL |
| | UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE |
| | BUILDING OR STRUCTURE. |
| | 225.32 LOCATION |
| | THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER |
| | INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED |
| | OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR |
| | STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A |
| | READILY ACCESSIBLE LOCATION NEAREST THE POINT OF |
| | ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS |
| | SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED. |
| | |
| | 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) |
| | OR BRANCH CIRCUIT(S) |
| | (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S) |
| | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A |
| | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM |
| | INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING |
| | ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE |
| | WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING |
| | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN 250.50 SHALL BE INSTALLED. |
| | |
| | INDICATE COMPLIANCE WITH THESE ARTICLES BY PROVIDING A |
| | RISER DIAGRAM |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |