2008-10-27 14:28:522004 FBC W/2007 REVISIONS
 CONSTRUCT DETACHED GARAGE
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE JOHNS-MANVILLE MODIFIED
 ROOFING SYSTEM THAT WAS SUBMITTED IS FOR THE 2007
 FLORIDA BUILDING CODE. THE CURRENT CODE IS THE 2004
 FBC. PLEASE SUBMIT TWO COPIES OF THE PRODUCT APPROVALS
 FOR THE 2004 FBC. FAC RULE 9B-72. NOTE: SPECIFY WHICH
 ONE OF THE APPROVED ASSEMBLIES AND FASTENING OPTION
 WILL BE USED LISTED IN THE PRODUCT APPROVAL WILL BE
 INSTALLED. IF THE DESIGN PRESSURE IS LESS THAN -89 PSF,
 THEN PROVIDE RAS 117 CALCULATIONS FOR THE ENHANCED
 FASTENING AT THE PERIMETER AND CORNER ROOF AREAS.
  
 2) THE PRODUCT APPROVAL FOR THE CLOPAY GARAGE DOOR IS
 NO LONGER CURRENT. SUBMIT TWO CURRENT STATE OR
 MIAMI-DADE PRODUCT APPROVALS FOR THE GARAGE DOOR AS
 REQUIRED BY FAC RULE 9B-72.
  