2009-02-03 09:58:52PLUMBING PLAN REVIEW:
 DENIED
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 ****FROM PREVIOUS REVIEW:
  
 1. CLEARLY INDICATE THE CORRECT CODE CYCLE ON THE
 PLANS.PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. THE
 CURRENT CODE CYCLE FOR THE PLANS IS 'FBC-2004 WITH 2007
 REVISIONS".
 ****NO WRITTEN RESPONSE, BUT HAND WRITTEN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 2. SHEET A1 SANITARY PLUMBING RISER: PLEASE CORRECT/ADD
 THE FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL STACK
 ON THE 1ST FLOOR FOR THE PROPOSED 2ND FLOOR PLUMBING.
 PER SECTION 708.3.4 BASE OF STACK.
 ****NO WRITTEN RESPONSE, BUT HAND DRAWN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 B} THE HORIZONTAL DRY VENT AT THE BIDET IS NOT ALLOWED.
 PER SECTION 905.3 VENT CONNECTIONS TO DRAINAGE SYSTEMS.
 ****NO WRITTEN RESPONSE, BUT HAND DRAWN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 3. SHEET A4 SECOND FLOOR PLAN IS INDICATING A STEAM
 SHOWER. PLEASE PROVIDE THE FOLLOWING INFORMATION
 COMPLIANT TO THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} CLEARLY INDICATE THE LOCATION OF THE STEAM SHOWER
 UNIT ON THE FLOOR PLAN. PER SECTION 106.1 SCOPE.
 ****NO WRITTEN RESPONSE, BUT HAND WRITTEN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 B} CLEARLY INDICATE THE POINT OF DISCHARGE OF THE
 TEMPERATURE AND PRESSURE RELIEF VALVE REQUIRED FOR THE
 STEAM UNIT. PER SECTION 504.6.1 DISCHARGE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 C} PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE STEAM UNIT. MANUFACTURE SHEETS
 SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 SUCH AS UL, ETL, ARS, CSA OR AGA. PER FBC-2004 CHAPTER
 1, (W.P.B. AS AMINDED) SECTION 106.1.2 ADDITIONAL DATA
 REQUIRED.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1B. WHITE OUT IS NOT APPROVED ON SIGNED & SEALED PLANS.
 SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NO RESPONSE TO THE TRANSMITTAL LETTER SUBMITTED.
  