| Date |
Text |
| 2008-10-30 16:19:04 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. CLEARLY INDICATE THE CORRECT CODE CYCLE ON THE |
| | PLANS. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND |
| | SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. THE |
| | CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH 2007 |
| | REVISIONS". |
| | |
| | 2. SHEET A1 SANITARY PLUMBING RISER: PLEASE CORRECT/ADD |
| | THE FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL STACK |
| | ON THE 1ST FLOOR FOR THE PROPOSED 2ND FLOOR PLUMBING. |
| | PER SECTION 708.3.4 BASE OF STACK. |
| | |
| | B} THE HORIZONTAL DRY VENT AT THE BIDET IS NOT ALLOWED. |
| | PER SECTION 905.3 VENT CONNECTIONS TO DRAINAGE SYSTEMS. |
| | |
| | 3. SHEET A4 SECOND FLOOR PLAN IS INDICATING A STEAM |
| | SHOWER. PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | COMPLIANT TO THE FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} CLEARLY INDICATE THE LOCATION OF THE STEAM SHOWER |
| | UNIT ON THE FLOOR PLAN. PER SECTION 601.1 SCOPE. |
| | |
| | B} CLEARLY INDICATE THE POINT OF DISCHARGE OF THE |
| | TEMPERATURE AND PRESSURE RELIEF VALVE REQUIRED FOR THE |
| | STEAM UNIT. PER SECTION 504.6.1 DISCHARGE. |
| | |
| | C} PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE STEAM UNIT. MANUFACTURE SHEETS |
| | SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER, AND A |
| | LSTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY |
| | SUCH AS UL, ETL, ARS, CSA, AGA. PER FBC-2004 CHAPTER 1, |
| | (W.P.B. AS AMENDED) SECTION 106.1.2 ADDITIONAL DATA |
| | REQUIRED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |