| 2008-10-28 11:02:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) PLEASE SHOW ON MECHANICAL PLAN THE LOCATION OF THE | | | CONDENSER UNIT, PER 2004 FBC/R M1307.3. | | | | | | 2) A.H.U. MODEL NUMBER FV4BNF030 LISTED ON THE A/C | | | EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI | | | DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI | | | CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1. | | | | | | 3) PLEASE SUBMIT ALL OF THE COOLING LOAD CALCULATIONS, | | | ONLY ONE PAGE OF THE CALCULATIONS WAS SUBMITTED, PER | | | 2004 FBC 13-607.1.ABC.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|