Plan Review Notes
Plan Review Notes For Permit 08100353
Permit Number 08100353
Review Stop M
Sequence Number 1
Notes
Date Text
2008-10-28 11:02:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE SHOW ON MECHANICAL PLAN THE LOCATION OF THE
 CONDENSER UNIT, PER 2004 FBC/R M1307.3.
  
 2) A.H.U. MODEL NUMBER FV4BNF030 LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 3) PLEASE SUBMIT ALL OF THE COOLING LOAD CALCULATIONS,
 ONLY ONE PAGE OF THE CALCULATIONS WAS SUBMITTED, PER
 2004 FBC 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]