| Plan Review Notes For Permit 08100353 |
| Permit Number |
08100353 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-24 13:54:18 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PANEL "A-1" ON SHEET "E1" IS LISTED AS MLO ON THE | | | SCHEDULE AND MCB ON THE RISER . CORRELATE SAME. | | | | | | 2} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND | | | 210.52(A)(2). 2005 NEC. SEE EXISTING STUDY AND LIBRARY. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1), NEW POWDER ROOM. | | | | | | 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), THESE CIRCUITS ARE NOT LISTED IN ANY | | | OF THE PANELS. | | | | | | 5} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|