Plan Review Notes
Plan Review Notes For Permit 08100353
Permit Number 08100353
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-31 16:57:58RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT
 PICK UP TO AVOID EXPIRATION OF IT.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD. (561)233-5120) TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE COMPLETE FRAMING WALL SECTION THRU ELEVATOR
 AND STAIRWAY SHAFT. SPECIFY ALL FRAMING MEMBERS AND
 FASTENERS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH SEC. R301.1 AND R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
 ALSO, PROVIDE COMPLETE FRAMING INFORMATION AND
 SPECIFICATIONS FOR SUPPORT OF ELEVATOR.
  
 4- PROVIDE SPECIFICATIONS FOR ROOF SHEATHING NAIL TYPE
 AND SPACING. INCLUDING NAILING AT ROOF ZONE #3 AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE. (NOTE: MIN. 8D RING SHANK NAILS ARE REQUIRED AND
 4" O.C. NAILS ARE REQUIRED ON ROOF ZONE 3).
  
 5- PROVIDE COMPLETE SPECIFICATIONS FOR ELEVATOR TO BE
 INSTALLED.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR ICYNENE
 INSULATION..
  
 7- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) EXTERIOR SWING DOOR. INFORMATION SUBMITTED FOR THE
 MASONITE FIBERGLASS DOOR IS NOT AN APPROVED PRODUCT
 APPROVAL.
  
 B) CASEMENT WINDOW. NOA 05-1129.11 SUBMITTED EXPIRED ON
 MAY 22, 2008. NEED TO PROVIDE CURRENT ONE.
  
 C) UNDERLAYMENT WATERPROOFING MEMBRANE ON SECOND FLOOR
 DECK. PRODUCT APPROVAL TO SHOW INSTALLATION OF TILE AS
 SPECIFIED ON PLANS.
  
 D) HARDIE TRIM FOR STEEL COLUMNS. PROVIDE
 SPECIFICATIONS OF ATTACHMENT TO STEEL COLUMN.
  
 8- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004. OWES $966.54
 FOR UPDATED VALUATION AND RADON FEES.
  
 9- ARCHITECT TO PROVIDE HIS LICENSE NUMBER ON THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
  
 10- PLANS NEED TO PROVIDE SPECIFICATIONS FOR TYPE OF
 DRYWALL TO BE USED TO SEPARATE GARAGE FROM BEDROOM
 ABOVE AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 11- LIMITATION #9 ON PRODUCT APPROVAL FOR METAL ROOFING
 UNDERLAYMENT FL3455-R1 STATES THAT ROOF NEEDS TO HAVE
 PROPER VENTILATION. PLANS CALL FOR ICYNENE INSULATION
 AND NO ATTIC VENTILATION. SPECIFY HOW PROVIDING ATTIC
 VENTILATION TO ALLOW THE USE OF THIS UNDERLAYMENT.
  
 12- REVISE THE ENERGY CALCULATIONS:
 A) CONDITIONED FLOOR AREA DOESN'T MATCH CONDITIONED
 FLOOR AREA SPECIFIED ON PLANS.
  
 B) MISSING THE FLOOR CONCRETE SLAB ON ITEM #8.
  
 C) MISSING THE GARAGE ADJACENT WALLS ON ITEM #9.
  
 D) MISSING THE ADJACENT GARAGE CEILING AREA ON ITEM
 #10.
  
 E) UNDER ATTIC AREA IS INCORRECT. REVISE AS REQUIRED.
  
 F) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 13- SOIL TEST REPORT:
 A) NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 B) REPORT NEEDS TO HAVE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 471 FLORIDA STATUTE.
  
 14- SHEET A1: UPDATE DESIGN CRITERIA. CURRENT REVISIONS
 TO FBC 2004 ARE 2007 REVISIONS NOT 2006. REVISE AS
 REQUIRED.
  
 15- SHEET A2:
 A) SPECIFY FIREBLOCKING ON WALL SECTION AS REQUIRED BY
 SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) WALL SECTION: SPECIFY ALL FASTENERS FOR BEARING
 WALLS BY STAIRWAY. TOP AND BOTTOM.
 ALSO, SPECIFY HOW LONG ARE THE 1/2" ANCHOR BOLTS AT
 BOTTOM PLATE. SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 C) SPECIFY SLOPE FOR UPPER DECK.
  
 16- SHEET A3: WALL SECTION 1/3 SHOWS 6" ICYNENE
 INSULATION ON 2X6 WALL. 2X6 WALL HAS 5 1/2" ACTUAL
 THICKNESS. REVISE AS REQUIRED.
  
 17- SHEET A4:
 A) WALL SECTION 1/4: SPECIFY ALL WALL CONNECTORS TO
 VERIFY COMPLIANCE WITH SEC. R301.1 AND R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 B) FLOOR FRAMING PLAN: SPECIFY ALL CONNECTORS AT THE
 ENDS OF ALL BEAMS (INCLUDING ONES SUPPORTED ON WOOD
 COLUMNS), GIRDER TRUSSES, FLOOR JOISTS, CANTILEVERED
 BALCONY JOISTS, ETC. TO VERIFY COMPLIANCE WITH SEC.
 R301.1 AND R601.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: CLEARLY SPECIFY SPECIFIC CONNECTORS.
 SPECIFYING "STRAPS" DOESN'T PROVIDE SPECIFIC
 INFORMATION TO VERIFY COMPLIANCE WITH PROPOSED STRAP
 INSTALLATION AND CALCULATED LOADS.
  
 C) SPECIFY FIREBLOCKING ON WALL SECTION 1/4 AS REQUIRED
 BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 18- SHEET A5:
 A) SPECIFY FIREBLOCKING IN ALL WALL SECTIONS AS
 REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) SPECIFY ALL FASTENERS IN WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. 301.1 AND R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 C) TOTAL LOAD FOR ROOF TRUSSES DON'T ADD UP. IT SHOULD
 BE 65PSF NOT 55PSF. REVISE AS REQUIRED.
  
 19- SHEET A6: SPECIFY ALL CONNECTORS IN WALL SECTION TO
 VERIFY COMPLIANCE WITH SEC. R301.1 AND R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  