| 2010-01-15 14:20:38 | |
| | ** DENIED 4TH REVIEW * |
| | |
| | ** SECOND REVIEW UNDER ACTUAL PERMIT APPLICATION. FIRST |
| | TWO REVIEWS WERE UNDER * PLAN REVIEW ONLY*. |
| | |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR THE SAME CODE SECTIONS NOTED ON |
| | EACH REVIEWS. THIS IS THE SECOND REVIEW UNDER ACTUAL |
| | PERMIT APPLICATION, IF PLANS COME BACK IN FOR ONE MORE |
| | REVIEW WITH THE SAME CODE COMPLIANCE COMMENTS NOTED A |
| | 4X FEE FOR THE PLAN REVIEW PORTION OF THE PERMIT FEE |
| | SHALL BE ASSESSED. THIS IS ONLY GIVEN AS A NOTICE AT |
| | THIS TIME. |
| | |
| | 2) NOTE: IN AN EFFORT TO ALLEVIATE FURTHER REVIEWS AND |
| | REPEAT COMMENTS THIS REVIEWER CALLED FIRM LISTED ON |
| | TITLE BLOCKS REQUESTING TO SPEAK TO THE ENGINEER OF |
| | RECORD. THE STAFF INDIVIDUAL FIRST STATED NO SUCH |
| | PERSON WORKED FOR THEIR FIRM. AFTER SEVERAL QUESTIONS, |
| | STAFF THEN STATED THIS ENGINEER WAS ACTUALLY AN OUTSIDE |
| | CONSULTANT AND DID NOT WORK FOR INTERPLAN. THE CALL WAS |
| | NOT RECEIVED WELL AND STAFF DID NOT SEEM TO KEEP |
| | ATTENTION TO CALL. CALL WAS TERMINATED BY REVIEWER AS |
| | NO ACCOMPLISHMENT WAS BEING MADE. |
| | ENGINEER OF RECORD SHALL LIST HIS OR HER INFORMATION ON |
| | TITLE BLOCK IF THEY ARE NOT UNDER THE DIRECT EMPLOYMENT |
| | OF FIRM LISTED. PLEASE CONTACT BOARD OF ENGINEERS AND |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| | THIS HAS BEEN CONFIRMED WITH FBPE. |
| | THE STATE HAD THE INFORMATION FOR ENGINEER OF RECORD IS |
| | WITH DESIGN PLUS INC. PLEASE PROVIDE CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS LISTED WITH THE STATE OF |
| | FLORIDA. |
| | |
| | DESIGN PLUS INC |
| | 664 OAK HOLLOW WAY |
| | ALTAMONTE SPRINGS, FL. 32714 |
| | CA # 26340 |
| | ** THIS INFORMATION IS REQUIRED ALSO ON MECHANICAL |
| | SHEETS. |
| | ** TO ALLEVIATE RE-PRINTING OF ALL SHEETS, THIS MAY BE |
| | ADDED BY A STAMP, TITLE BLOCK STICKER OR NEATLY |
| | HANDWRITTEN. |
| | |
| | PLEASE PROVIDE REVISED TITLE BLOCK FOR ENGINEER OF |
| | RECORD. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002, FS 471.025, 471.023. |
| | |
| | 3) NOTE: AS REQUESTED ON ALL PREVIOUS REVIEWS PLEASE BE |
| | SURE TO SEE FBC 13-415.AB.5, 13-415.AB.2.2 AND |
| | 13-400.0.A, 13-101.1.1 |
| | PLEASE BE SURE ALL SYSTEMS, COMPONENTS AND ITEMS ON |
| | PLANS WHICH AFFECT THE ENERGY CONSUMPTION AND |
| | EFFICIENCY OF THE BUILDING ARE PLACED INTO THE INPUT |
| | DATA REPORT OF THE SUBMITTED CALCULATIONS. |
| | A) ALL EXTERIOR LIGHTING IS REQUIRED TO BE PLACED INTO |
| | THE IDR. THIS WAS SPECIFICALLY MENTIONED ON THE |
| | PREVIOUS REVIEW YET THERE ARE SOME FIXTURES STILL NOT |
| | PART OF THE IDR. THE SAME FIXTURES WERE NOTED ABOVE A |
| | CALL WAS PLACED TO FIRM TO FIND OUT WHERE ALL OF THE |
| | 1000W FIXTURES AND 400WATT FIXTURES ARE FED FROM. THESE |
| | ARE SHOWN ON SITE PHOTO-METRICS, HOWEVER NONE OF THESE |
| | FIXTURES ARE IN THE IDR. |
| | PLEASE E-0 INDICATES 3 MWD FIXTURES ON EXTERIOR WALLS |
| | HOWEVER LIGHTING PLANS ONLY INDICATE ONE OF THESE |
| | FIXTURES? THE ADDITIONAL FIXTURES ARE NOT IN THE IDR |
| | EITHER? |
| | CIRCUITING? CIRCUITING ON SCHEDULES? |
| | ONLY THE MINIMUM NEEDS TO BE SHOWN AT THIS TIME. |
| | |
| | 4) NOTE: PREVIOUS NOTE WITH RESPECT TO 250.94 AND |
| | INTERSYSTEM BONDING WAS ADDRESSED BY A SPEC SHEET FOR |
| | SPECIFICATION BOOK. PLEASE PROVIDE ON PLANS. |
| | SPECIFICATION BOOKS ARE NOT USED FOR INSPECTIONS. |
| | IF THIS IS THE ONLY COMMENT WHICH NEEDS TO BE DONE, |
| | PLANS CAN BE REDLINED WITH THIS INFORMATION FROM |
| | REVIEWER AND REVISED AT A LATER DATE. |
| | |
| | 5) NOTE: PREVIOUS NOTE WITH RESPECT TO 406.8 WAS NOT |
| | REVISED ON PLANS. RESPONSE MENTION NOTED ADDED TO SHEET |
| | E-4 HOWEVER NOTE COULD NOT BE FOUND. THIS CAN ALSO BE |
| | RED-LINED WITHOUT REVISING SHEET. |
| | |
| | 6) NOTE: PREVIOUS NOTE #8, RESPONSE MENTIONS TO BE |
| | HARD-WIRED, HOWEVER PLEASE KNOW THIS STILL DOES NOT |
| | ALLOW THE USE OF CORDS. |
| | THIS CAN BE REDLINED ON PLANS. PLEASE BE SURE TO VERIFY |
| | LISTING OF EQUIPMENT SO THAT LISTING IS NOT VOIDED. |
| | 400.8(2) |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |