| Date |
Text |
| 2008-11-03 14:53:15 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODES |
| | |
| | 1. ALL SHEETS. THE TITLE BLOCKS SHALL INDICATE THE |
| | CORRECT ADDRESS WHICH IS 8132 OKEECHOBEE BLVD, NOT JUST |
| | OKEECHOBEE ROAD AS SHOWN. SECTION 106.1.1. |
| | |
| | 2. SHT AO THE CODE INFORMATION SHALL INCLUDE THE 2005, |
| | 2006 & 2007 REVISIONS/AMENDMENTS. SECTION 106.1.1. |
| | |
| | 3. SHT A1 THE SINK IN ROOM 111 SHALL BE ACCESSIBLE. |
| | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.24 WITH ALL SUBSECTIONS. FORWARD APPROACH CLEAR |
| | FLOOR SPACE IS REQUIRED AND CABINET DOORS ARE NOT |
| | APPROVED IN THE CLEAR FLOOR SPACE. |
| | |
| | 4. SHTS A3 & A4.1 INDICATE THE SIZE OF THE GUTTERS AND |
| | DOWNSPOUTS. TABLES 1106.3 & 1106.6. |
| | |
| | 5. SHT A8 DETAILS 8 & 10 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | ___W/C'S: |
| | A. 11-4.16.5 FLUSH CONTROLS (SHOWN ON WALL SIDE). |
| | ___LAVS: |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.7 FAUCETS |
| | |
| | 6. SHT A8 DETAILS 8 & 9. PER SECTION 1210.2 WALLS |
| | WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET. 3 FT 4 |
| | INCHES IS SHOWN. |
| | |
| | 7. SHT A10 ELEVATION 5. SHOW COMPLIANCE WITH SECTION |
| | 11-4.24. (SEE COMMENT 3). |
| | |
| | 8. ALL P, M & E SHEETS. PER FAC 61G15-23.002(1)(2) A |
| | PROFESSIONAL ENGINEER SHALL SIGN HIS NAME & AFFIX HIS |
| | SEAL TO ALL PLANS. IT APPEARS THAT AN INITIAL HAS BEEN |
| | USED IN PLACE OF THE REQUIRED SIGNATURE. IF INDEED THIS |
| | IS THE LEGAL SIGNATURE OF THE ENGINEER OF RECORD, THEN |
| | A SIGNED, SEALED, DATED, NOTORIZED LETTER INDICATING |
| | THE LEGAL SIGNATURE FOR OUR RECORDS SHALL BE SUBMITTED. |
| | FS 471.025. |
| | |
| | 9. SHT P-1 FD-2 IN THE MECHANICAL ROOM IS NOT APPROVED |
| | FOR CONDENSATE DRAINAGE. ARTICLE III SECTION |
| | 90-125(B)(5) . PLEASE SUBMIT INFORMATION/RISER SHOWING |
| | THE APPROVED DISPOSAL OF THE CONDENSATE. (PLANTED AREA, |
| | STORM LINE, DRYWELL ETC.) (MINIMUM 1 FOOT OFF STRUCTURE |
| | WALL REQUIRED. 1503.6). |
| | |
| | 10. SHT P1 PLUMBING FLOOR PLAN DOES NOT SHOW THE RISER |
| | AND PIPING FOR THE LAVS AS INDICATED ON THE WASTE & |
| | VENT RISER DIAGRAM. PLEASE SHOW THE SANT. PIPING AND |
| | RISER FOR THE LAVS ON THE FLOOR PLAN TO CORRELATE WITH |
| | THE RISER DIAGRAM. SECTIONS 106.1.1 & 701.1. |
| | |
| | 11. SHT P2 THE WATER HAMMER ARRESTORS SHALL BE |
| | INSTALLED NEAR THE FIXTURES IN AN EFFECTIVE RANGE NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |