| 2008-10-23 12:05:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | FOR PLAN REVIEW NOT FOR PERMIT. |
| | *** DENIED *** |
| | |
| | 1) ENERGY CALCULATIONS SYSTEM REPORT NEEDS TO LIST EACH |
| | SYSTEM INDIVIDUALITY NOT COMBINE THEM TOGETHER, PER |
| | 2004 FBC 13-407.2.A. |
| | |
| | 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 |
| | FBC 13-407.1.ABC.1. |
| | |
| | 3) A/C SYSTEM HP-1 HP-2 WITH AHU-1 AND CU-1 WITH AC-1 |
| | MODEL NUMBERS LISTED ON THE A/C EQUIPMENT SCHEDULE |
| | COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, |
| | PLEASE SUBMIT AN ARI CERTIFICATE OR MANUFACTURE SPEC. |
| | SHEETS, PER 2004 FBC 13-407.1.ABC.3.1.1. |
| | |
| | 4) PLAN M0 AIR HANDLER SCHEDULE NOTE STATES ROUTE |
| | CONDENSATE PIPE TO FLOOR DRAIN, PLAN M1 SECTION 'A-A' |
| | STATES CONDENSATE LINE TO FLOOR DRAIN, AND PLAN M2 |
| | CEILING HUNG A/H DETAIL STATES CONDENSATE DRAIN TO MOP |
| | SINK. PLEASE REMOVE THESE NOTES FROM THE PLANS AS |
| | CONDENSATE WATER MAY NOT DISCHARGE INTO THE CITY'S |
| | WASTE WATER FACILITY, PER CITY OF WEST PALM BEACH CITY |
| | CODE 90-125 (B) (5). PLEASE SHOW ON PLANS FOR |
| | CONDENSATE WATER TO DISCHARGE OUTDOORS TO AN |
| | APPROPRIATE LOCATION, PER 2004 FBC/M 307.2.1. |
| | |
| | 5) AHU-1 AND AHU-2 WILL REQUIRE SMOKE DETECTORS AT THE |
| | SUPPLY AND RETURN, PER 2004 FBC 606.2.2 COMMON SUPPLY, |
| | RETURN AIR AND SUPPLY AIR SYSTEMS. WHERE MULTIPLE |
| | AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY OR RETURN AIR |
| | DUCTS OR PLENUMS WITH A COMBINED DESIGN CAPACITY |
| | GREATER THAN 2,000 CFM (0.9 M 3 /S), THE RETURN AIR AND |
| | SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE |
| | DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. PLEASE |
| | SHOW ON MECHANICAL PLAN. |
| | |
| | 6) PLEASE ADD A NOTE TO PLAN M1. PER 2004 FBC/M 602.2.1 |
| | MATERIALS EXPOSED WITHIN PLENUMS. EXCEPT AS REQUIRED BY |
| | SECTIONS 602.2.1.1 THROUGH 602.2.1.5 , MATERIALS |
| | EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL |
| | HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E 84. |
| | |
| | 7) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR |
| | ENERTECH DC-FL LOUVERS, PER FS 553.842(1) AND FAC RULE |
| | 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | *** PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW |
| | STAMP AND SIGNATURE WILL MEET THIS REQUIREMENT). SEE |
| | W.P.B. AMEND. 106.3. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |