| 2008-11-12 10:59:20 | ***DENIED*** |
| | |
| | PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW AND NOT FOR |
| | PERMIT |
| | |
| | 1) CS SHEET IDENTIFIES ADDRESS AS OKEECHOBEE ROAD. |
| | PLEASE CORRECT ADDRESS TO READ OKEECHOBEE BLVD. AND ADD |
| | NUMERICAL OF BUILDING. |
| | |
| | 2) ADDRESS OF PROJECT TO BE PROVIDED IN TITLE BLOCK OF |
| | EACH SHEET SUBMITTED. |
| | |
| | 3) PROVISIONS FOR AFTER NORMAL BUSINESS HOURS ACCESS TO |
| | BE ADDRESSED EITH BY KNOX BOX ENTRY SYSTEM OR OTHER |
| | APPROVED SECURED MEANS. |
| | |
| | 4) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE |
| | MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH |
| | BACKGROUND. PLEASE ADD NOTE TO ELEVATIONS ON SHEET A3. |
| | |
| | 5) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| | REQUIRED TO BE MOUNTED AT LOCATIONS NOT TO EXCEED |
| | MINIMUM 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 6) INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION |
| | FOR WALLS AND CEILING PER 101, SEC. 38.3.3.2. |
| | |
| | 7) DUCT SMOKE DETECTORS SHALL BE TIED INTO THE BUILDING |
| | FIRE ALARM SYSTEM WHEN APPLICABLE. IF NO FIRE ALARM |
| | SYSTEM IS PROVIDED, AUDIBLE/VISUAL APPLIANCES ARE STILL |
| | REQUIRED FOR LOCAL OCCUPANT NOTIFICATION. |
| | |
| | 8) ALL EXIT DOORS SHALL COMPLY WITH 101, SEC. 7.2.1.5 |
| | LOCKS, LATCHES AND ALARMS. |
| | |
| | 9) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | |
| | ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER |
| | INDICATING HOW AND WHERE ON EACH SHEET EACH COMMENT WAS |
| | ADDRESSED WOULD HELP TO EXPEDITE THE PLAN REVIEW |
| | PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, ASST. FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |