| 2008-10-31 17:00:53 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PROJECT INFORMATION HAS BEEN FORWARDED TO THE |
| | ADDRESSING REVIEW TO CORRECT ADDRESS DISCREPANCIES. THE |
| | APPLIED LOCATION IS 8132 W OKEECHOBEE BLVD HOWEVER THE |
| | PLANS AND OTHER SUPPORTING DOCUMENTS SUCH AS ENERGY |
| | CALCULATIONS STATE OKEECHOBEE ROAD WHICH IS AN ENTIRELY |
| | DIFFERENT LOCATION AND STREET. |
| | PLEASE ADJUST PLANS AND CORRECT ADDRESS ONCE FINAL |
| | DETERMINATION IS MADE. |
| | FBC 106.5 |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS HAVE COME IN FOR PLAN |
| | REVIEW ONLY AND HAS NOT BEEN SUBMITTED FOR PERMIT. ONCE |
| | PLANS MEET CODE COMPLIANCE AND PERMIT APPLICATION HAS |
| | NOT BEEN MADE THE REVIEW WILL STILL REMAIN IN A FAILED |
| | STATUS UNTIL PERMIT APPLICATION IS MADE. THE LICENSING |
| | OF ALL DESIGNERS AND CONTRACTORS WILL BE VERIFIED AT |
| | THAT POINT. |
| | |
| | 3) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY |
| | CALCULATIONS AND THE INPUT DATA REPORT COORDINATES WITH |
| | THE SUBMITTED. PLANS. THE NUMBER OF FIXTURES, THE TYPE |
| | OF FIXTURES, THE WATTAGES AND THE CONTROLS NEED TO |
| | MATCH WITH THE PLANS. |
| | THE IDR SHOWS FOR INTERIOR LIGHTS A TOTAL OF THREE |
| | FIXTURES WHICH IS NOT POSSIBLE BASED ON THE PLANS. THE |
| | IDR STATES CLEARLY AT THE TOP OF THE LIGHTING FIELD *** |
| | NO OF LUMINAIRES*, ** WATTS PER LUMINAIRE* ETC. THIS |
| | DOES NOT INCLUDE ANY IDENTIFICATION OF USING JUST ONE |
| | FIXTURE AND A TOTAL. BASED ON THE PLANS SUBMITTED EVEN |
| | IF USING ONE TOTAL WATTAGE THE AMOUNT WOULD STILL NOT |
| | CORRELATE. |
| | PLEASE REVISE AND ADJUST ALL. |
| | PLEASE BE SURE TO SEE THE SPECIFIC SECTIONS BELOW FOR |
| | INTERIOR ALLOWANCES AND HOW VA LOADS OF FIXTURES AND |
| | ANY TRACK IS REQUIRED TO BE ENTERED. |
| | 13-400.3A, 13-101, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3. |
| | |
| | |
| | 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | ON PLANS AS WELL AS ON ELECTRICAL PLANS. SOME CODES |
| | REFERENCES ON PLANS ARE NO LONGER ADOPTED BY THE STATE |
| | OF FLORIDA AND HAVE NOT BEEN FOR OVER A DECADE. PLEASE |
| | SEE SHEET E1 FOR EXAMPLE WHICH STATES THE *1996 |
| | NATIONAL ELECTRICAL CODE**. PLEASE BE SURE TO CORRECT |
| | CODES REFLECTED ON PLANS. |
| | THE FOLLOWING SHALL BE LISTED AT A MINIMUM FOR THIS |
| | REVIEWER AND FOR THIS TRADE. |
| | |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHEN APPLICABLE) |
| | |
| | 5) NOTE: ( FOR CONTRACTOR) |
| | THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK SHALL |
| | INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT |
| | ETC EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. |
| | FBC 108.3 |
| | |
| | 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | FOR THE PROPOSED UPS. 90.7,110.3 |
| | |
| | 7) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | FOR THE PROPOSED MTS. 90.7,110.3. |
| | |
| | 8) NOTE: PLEASE KNOW SEPARATE SYSTEMS SUCH AS THE LOW |
| | VOLTAGE FOR CAMERAS, PHONE, DATA ETC SHALL BE UNDER A |
| | SEPARATE PERMIT. THE LV FOR SECURITY WILL ALSO BE UNDER |
| | A SEPARATE PERMIT. THE SECURITY SYSTEM SHOP DRAWINGS |
| | SHOWING SPECIFICS ARE NOT REQUIRED BY THIS OFFICE IN |
| | FAC T HAVING THESE PLANS ON RECORD FILE FOR PUBLIC |
| | ACCESS IS NOT REQUIRED. BASE PLANS SHOWING CAMERA |
| | LOCATIONS, ANY ACCESS CONTROLS IS REQUIRED. PLEASE CALL |
| | TO GO OVER SPECIFICS OR FOR ANY QUESTIONS REGARDING |
| | SYSTEMS. |
| | **FBC 105.1, 106.1.1 |
| | |
| | 9) NOTE: PLEASE COMPLETE PLANS WITH PANEL SCHEDULES AND |
| | LOAD CALCULATIONS. CIRCUITING AND OTHER ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE VERIFIED FOR CODE COMPLIANCE AT |
| | THIS TIME. |
| | 220, 408.4, 240.4, 310.16 ETC |
| | FBC 106.1.1, 106.1.2 |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |