| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-20 11:23:45 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. COOLING LOAD CALCULATIONS WERE NOT PROVIDED WITH | | | THIS SUBMISSION. COOLING LOAD CALCULATIONS SHALL BE | | | APPENDED TO THE ENERGY CALCULATIONS IN ACCORDANCE WITH | | | FBCB 13-407.1.ABC.1.1. | | | | | | 2. OUTSIDE AIR CALCULATIONS DO NOT CORRESPOND WITH THE | | | REQUIREMENTS OF FBCM TABLE 403.3. THE OCCUPANCY | | | CLASSIFICATION AND OCCUPANT LOAD AS STATED IN THE TABLE | | | SHALL BE USED WHEN CALCULATING OUTSIDE AIR | | | REQUIREMENTS. ALSO, THE PLANS SHOW THE 150 CFM OF | | | EXHAUST AS ADDED TO THE OUTSIDE AIR FOR THE TOTAL. THE | | | INCLUSION OF EXHAUST IN THE BATHROOMS DOES NOT INCREASE | | | THE AMOUNT OF OUTSIDE AIR SUPPLIED AND SHOULD NOT BE | | | PART OF THE TOTAL. | | | | | | 3. THSES PLANS WERE DRAWN AND DESIGNED BY AN AC | | | CONTRACTOR. THIS PROJECT IS FOR A BUILDING WITH AN | | | OCCUPANT LOAD IN EXESS OF 100 PERSONS AND THEREFOR | | | REQUIRES THE SYSTEMS TO BE DESIGNED BY AN ENGINEER IN | | | ACCORDANCE WITH FLORIDA STATUTE 471.003. PROVIDE AC | | | PLANS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER | | | LICENSED IN ACCORDANCE WITH THIS STATUTE. | | | | | | 4. PLEASE SEE ELECTRICAL COMMENTS REGARDING THE VERSION | | | OF ENERGY CALCULATIONS WHICH WERE SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|