| 2008-11-03 13:42:45 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: COORDINATION OF THE SUBMITTED INPUT DATA |
| | REPORT WITH THE ENERGY CALCULATIONS IS NEED. FOR |
| | EXAMPLE PLEASE SEE THE PLANS WHICH INDICATE NEW SURFACE |
| | MOUNTED FIXTURES ALONG WALK YET THE FIXTURE LEGEND DOES |
| | NOT INDICATE THESE SAME FIXTURES. |
| | 13-415.2.ABC.1.3. |
| | ** SEE NOTES FORM OTHER TRADES. |
| | |
| | 2) NOTE: PER BUILDING REVIEW COMMENTS: IF THIS IS GOING |
| | TO BE CONSIDERED A SEPARATE BUILDING AS THE PLANS |
| | INDICATE A 4HR RATED FIRE WALL THEN BY THE DEFINITIONS |
| | SET FORTH IN THE FBC, PLEASE INDICATE ELECTRICAL WITH A |
| | SEPARATE BUILDING PER 225.31-225.39. |
| | IT IS UNCLEAR IF THIS IS THE INTENT OF THE DESIGN TO |
| | CONSIDER THIS *ADDITION* AS A SEPARATE BUILDING. THIS |
| | WOULD GREATLY AFFECT THE WAY THE ELECTRICAL IS |
| | CURRENTLY SHOWN. ON PREVIOUS PLANS IT WAS AN ADDITION |
| | NOT A *SEPARATE BUILDING*. |
| | 300.21, FBC DEFINITIONS AND NEC DEFINITIONS. |
| | |
| | 3) NOTE: PLEASE COORDINATE RISER. RISER NOTES TWO PANEL |
| | *C*. |
| | PLEASE SEE DIAGRAM IN CENTER OF PAGE AT THE TOP WHICH |
| | CALLS FOR 2-200AMP PANELS AND ONE 125AMP PANEL HOWEVER |
| | NO 100AMP PANELS. |
| | 215.5.230,240, ETC |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |