| 2008-10-21 15:07:57 | |
| | |
| | DENIED |
| | |
| | 1) SHUTTER PERMIT APPLICATIONS REQUIRE 2 COPIES OF A |
| | KEY PLAN (WITH EGRESS AND OPENING SIZES SHOWN), SHUTTER |
| | SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS |
| | SHALL BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE |
| | AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT |
| | INFORMATION SPECIFIC TO THE SITE (DESIGN PRESSURE, |
| | ZONE, TYPE OF CONSTRUCTION, MOUNTING CONNECTION METHOD, |
| | ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR HORIZONTAL), |
| | ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE. |
| | |
| | 2) SHUTTER INSTALLATION: (FASTENERS FOR FILLED CELL |
| | BLOCK-WORK) - CONTRACTOR CANNOT ASSUME THAT THERE IS A |
| | CONCRETE SUBSTRATE WHEN SELECTING FASTENERS (AND |
| | SPACING) UNLESS THEY CAN PROVIDE DOCUMENTATION TO |
| | VERIFY COMPRESSIVE STRENGTH OF 3,000 PSI, OR 3,500 PSI, |
| | ETC, AND THE REQUIRED FASTENER EMBEDMENT DEPTH,AS |
| | REQUIRED ON THE PRODUCT APPROVAL. IF DOCUMENTATION IS |
| | NOT PROVIDED THE SUBSTRATE SHALL BE CONSIDERED MASONRY |
| | AND THE O/C SPACING SHOULD BE ADJUSTED ACCORDINGLY. |
| | |
| | 3) THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE |
| | BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS |
| | DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN |
| | GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600 |
| | FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C |
| | CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND |
| | PRESSURES ACCORDINGLY. |
| | |