2008-10-21 15:07:57 
  
 DENIED
  
 1) SHUTTER PERMIT APPLICATIONS REQUIRE 2 COPIES OF A
 KEY PLAN (WITH EGRESS AND OPENING SIZES SHOWN), SHUTTER
 SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS
 SHALL BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE
 AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT
 INFORMATION SPECIFIC TO THE SITE (DESIGN PRESSURE,
 ZONE, TYPE OF CONSTRUCTION, MOUNTING CONNECTION METHOD,
 ANCHOR TYPE, SHUTTER SPAN (VERTICAL OR HORIZONTAL),
 ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE.
  
 2) SHUTTER INSTALLATION: (FASTENERS FOR FILLED CELL
 BLOCK-WORK) - CONTRACTOR CANNOT ASSUME THAT THERE IS A
 CONCRETE SUBSTRATE WHEN SELECTING FASTENERS (AND
 SPACING) UNLESS THEY CAN PROVIDE DOCUMENTATION TO
 VERIFY COMPRESSIVE STRENGTH OF 3,000 PSI, OR 3,500 PSI,
 ETC, AND THE REQUIRED FASTENER EMBEDMENT DEPTH,AS
 REQUIRED ON THE PRODUCT APPROVAL. IF DOCUMENTATION IS
 NOT PROVIDED THE SUBSTRATE SHALL BE CONSIDERED MASONRY
 AND THE O/C SPACING SHOULD BE ADJUSTED ACCORDINGLY.
  
 3) THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE
 BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS
 DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN
 GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600
 FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C
 CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND
 PRESSURES ACCORDINGLY.
  
 BLDG PLAN REVIEW