| Plan Review Notes For Permit 08100312 |
| Permit Number |
08100312 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-10-16 09:11:56 | RESIDENTIAL SHUTTERS BUILDING REVIEW SECOND CHECKLIST. | | | REVIEW UNDER 2004 FBC CODE WITH 2007 REVISIONS. | | | | | | 1- STILL MISSING THE INSTALLATION SCHEDULE REQUESTED ON | | | PHONE CONVERSATION. | | | | | | 2- FAXED INFORMATION IS MISMATCHING. DRAWINGS NO 05-578 | | | SUBMITTED DOESN'T CORRESPOND TO EVALUATION REPORT | | | FL8465 SUBMITTED. GO TO WWW.FLORIDABUILDING.ORG AND | | | DOWNLOAD DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT | | | APPROVAL REPORT FL8465. | | | | | | 3- CLEARLY MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITION. EG: WALL MOUNTED, BUILT OUT, ETC. DRAWINGS | | | SUBMITTED HAVE CIRCLE THE INDIVIDUAL COMPONENTS ONLY. | | | EG: #1 WALL HEADER AND #7 BASE SILL. NEED TO MARK THE | | | SPECIFIC ASSEMBLY. SEE SHEETS 5 AND 6 OF DRAWINGS | | | SUBMITTED. | | | | | | 4- ANCHOR SCHEDULE CIRCLED ON PAGE 7 OF DRAWINGS | | | SUBMITTED IS FOR CONCRETE SUBSTRATE ONLY. AS DISCUSSED | | | ON PHONE CONVERSATION THIS SCHEDULE CAN BE USED FOR TOP | | | CONNECTIONS IF OPENING LINTEL OR CONCRETE TIE BEAM | | | EXISTS. FOR BOTTOM CONNECTION OF WINDOW OPENINGS IS | | | CONSERVATIVE TO USE THE CONCRETE BLOCK ANCHOR SCHEDULE | | | OR PROVIDE PROOF THAT EXISTING SUBSTRATE IS CONCRETE | | | WITH THE STRENGTH REQUIRED ON THE PRODUCT APPROVAL. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|