Plan Review Notes
Plan Review Notes For Permit 08100312
Permit Number 08100312
Review Stop B
Sequence Number 2
Notes
Date Text
2008-10-16 09:11:56RESIDENTIAL SHUTTERS BUILDING REVIEW SECOND CHECKLIST.
 REVIEW UNDER 2004 FBC CODE WITH 2007 REVISIONS.
  
 1- STILL MISSING THE INSTALLATION SCHEDULE REQUESTED ON
 PHONE CONVERSATION.
  
 2- FAXED INFORMATION IS MISMATCHING. DRAWINGS NO 05-578
 SUBMITTED DOESN'T CORRESPOND TO EVALUATION REPORT
 FL8465 SUBMITTED. GO TO WWW.FLORIDABUILDING.ORG AND
 DOWNLOAD DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL REPORT FL8465.
  
 3- CLEARLY MARK ON DRAWINGS SPECIFIC MOUNTING
 CONDITION. EG: WALL MOUNTED, BUILT OUT, ETC. DRAWINGS
 SUBMITTED HAVE CIRCLE THE INDIVIDUAL COMPONENTS ONLY.
 EG: #1 WALL HEADER AND #7 BASE SILL. NEED TO MARK THE
 SPECIFIC ASSEMBLY. SEE SHEETS 5 AND 6 OF DRAWINGS
 SUBMITTED.
  
 4- ANCHOR SCHEDULE CIRCLED ON PAGE 7 OF DRAWINGS
 SUBMITTED IS FOR CONCRETE SUBSTRATE ONLY. AS DISCUSSED
 ON PHONE CONVERSATION THIS SCHEDULE CAN BE USED FOR TOP
 CONNECTIONS IF OPENING LINTEL OR CONCRETE TIE BEAM
 EXISTS. FOR BOTTOM CONNECTION OF WINDOW OPENINGS IS
 CONSERVATIVE TO USE THE CONCRETE BLOCK ANCHOR SCHEDULE
 OR PROVIDE PROOF THAT EXISTING SUBSTRATE IS CONCRETE
 WITH THE STRENGTH REQUIRED ON THE PRODUCT APPROVAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712