Plan Review Notes
Plan Review Notes For Permit 08100312
Permit Number 08100312
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-15 11:20:17RESIDENTIAL SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE COMPLETE INSTALLATION SCHEDULE AS REQUIRED
 BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS
 IMPACT PROTECTION. SEE ATTACHED COPY.
  
 2- PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72 FOR THE ACCORDION SHUTTERS.
 PROVIDE COVER PAGES AND DRAWINGS THAT WERE SUBMITTED
 FOR APPROVAL. DRAWINGS 08-225 SUBMITTED ARE NOT A 2004
 CODE VERSION APPROVED PRODUCT APPROVAL AND ARE MISSING
 THE COVER PAGES.
 PLEASE MAKE SURE PRODUCT APPROVAL SUBMITTED IS FOR 2004
 CODE VERSION, WHICH IS THE CURRENT CODE IN EFFECT.
  
 3- ON ACCORDION DRAWINGS CLEARLY MARK SPECIFIC MOUNTING
 CONDITIONS ( EG: WALL MOUNT SECTION, CEILING MOUNT
 SECTION, WALL BUILD OUT SECTION, ETC) TO VERIFY
 COMPLIANCE WITH PROPOSED CONNECTION TYPE AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE AND PANEL SPAN.
  
 4- PLEASE MAKE SURE CORRECT ANCHOR SCHEDULE FROM
 SHUTTERS DRAWINGS IS USED. THIS BUILDING IS NOT A
 CONCRETE BUILDING. CHECK IF BUILDING IS CONCRETE BLOCK
 AND WOOD FRAMING ON THE SECOND FLOOR AND USE
 CORRESPONDING ANCHOR SCHEDULE. CONCRETE SCHEDULE MAY BE
 USED ON TOP CONNECTION IF THE OPENING LINTEL IS PRECAST
 LINTEL OR PART OF A CONCRETE TIE BEAM. USE CONCRETE
 BLOCK ANCHOR SCHEDULE ON BOTTOM CONNECTION (USE WOOD
 ANCHOR SCHEDULE FOR WOOD FRAMING). OTHERWISE, PROVIDE
 TESTING SHOWING THAT WINDOW SILLS ARE CONCRETE WITH THE
 REQUIRED STRENGTH AS SHOWN ON SHUTTERS DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712