| Notes |
| Date |
Text |
| 2008-10-16 08:34:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. A CONCRETE BLOCK SUBSTRATE REQUIRES USE OF THE | | | ANCHOR CHART ON SHEET 9 OF THE NOA. SEE OPENING 4; 47.2 | | | PSF WOULD REQUIRE 11" ANCHOR SPACING RATHER THAN THE | | | 18" SPECIFIED ON THE INSTALLATION SCHEDULE. PLEASE | | | REVISE. | | | | | | THIS COMMENT APPLIES TO OTHER OPENINGS. PLEASE CHECK | | | ALL. | | | |
|