2008-12-01 09:17:07 
 ** FAILED 2ND REVIEW **
  
 SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
  
  
  
 1) NOTE: PLEASE SEE RISER AND PLANS STILL DO NOT
 COORDINATE WITH THE ADDRESS OF THIS PROJECT FOR THIS
 TENANT.
 THE RISER DIAGRAM FOR EXAMPLE STILL INDICATES
 ELECTRICAL TO BE IN SPACE 1719 AND 1723 WHEN THE
 APPLIED LOCATION IS 1727 OKEECHOBEE RD.
 IN FACT THE RISER DOES NOT SHOW IN NOTES OR IN RISER
 ANY ELECTRICAL WHICH ACTUALLY HAS 1727 AS THE LOCATION.
 PLEASE COMPLETE THE RISER WITH ALL ELECTRICAL WHICH
 WILL BE LOCATED IN THIS NEW SPACE OF 1727. THIS
 INCLUDES ALL OTHER EXISTING ELECTRICAL SYSTEMS WHICH
 WILL NO LONGER BE A PART OF ANY OTHER TENANT SPACE.
 PLEASE SEE PLANS SUCH AS THE EXISTING PANELS IN 1719
 AND 1723 WHICH WILL NOW BE PART OF 1727.
 PLEASE COMPLETE RISER WITH ALL ELECTRICAL.
 PLEASE BE SURE TO LABEL ALL TENANT DISCONNECTS. RISER
 SHOWS WHAT WOULD APPEAR TO BE ONE NEW AND ONE EXISTING
 FED FROM NEW METER HOWEVER THIS IS NOT THE CASE. THE
 OTHER ELECTRICAL SYSTEMS IN THE SAME TENANT SPACE WOULD
 ALL BE PART OF TENANT AND WOULD REQUIRED DISCONNECTING
 MEANS TO BE LABELED.
 230.2E., 230.70,230.71,230.76,230.79, 215.5 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY OF PLANS AND COORDINATION.
  
 ** THE NEED OF COORDINATION OF THIS EQUIPMENT IS VITAL
 FOR SAFETY OF THE OCCUPANTS AS WELL AS ANY OTHER
 PERSONNEL. IN THE EVEN OF AN EMERGENCY AND FIRE
 DEPARTMENT PERSONNEL NEEDED TO SHUT DOWN POWER TO SPACE
 1727, THE DISCONNECTS AS SHOWN ON RISER AS SHOWN WOULD
 NOT BE LABELED AS NEEDED. IN FACT SOME WOULD SHOW 1723,
 AND 1719 COULD BE MISTAKEN FOR ANOTHER TENANT.
 THIS IS A LIFE SAFETY HAZARD AND NEEDS TO BE ADDRESSED.
  
 2) NOTE: THE VALUE FOR THE SCOPE OF WORK WAS INCREASED
 ON PERMIT APPLICATION AND BALANCE OF $721.50 WILL BE
 DUE BEFORE PERMIT ISSUANCE.
  
 3) NOTE: THE NEW TRANSFORMER DOES NOT SHOW ANY
 GROUNDING ATTACHMENT LOCATION PER 250.50,250.20,250.30
 ETC.
 PREVIOUS REVIEW:
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR NEW EQUIPMENT, CONTROL PANEL. PLEASE BE SURE
 LISTING FROM A NRTL IS LOCATED ON EQUIPMENT SHEETS.
 110.3,90.7.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved