Plan Review Notes
Plan Review Notes For Permit 08100299
Permit Number 08100299
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-31 14:47:49 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PROJECT INFORMATION HAS BEEN FORWARDED TO THE
 ADDRESSING REVIEW TO CORRECT ADDRESS DISCREPANCIES. THE
 APPLIED LOCATION IS 1701 OLD OKEECHOBEE. THE *OLD* IS
 NOT AN ACCURATE LOCATION AND THE ADDRESS IS *OKEECHOBEE
 RD*. THIS OFFICE IS WELL AWARE OF THE STREET SIGNS
 WHICH MAY CONTAIN THE WORDING OF *OLD* HOWEVER
 OKEECHOBEE RD IS THE LEGAL ADDRESS. ONCE THE CORRECT
 ADDRESS AND UNIT HAS BEEN DETERMINED PLEASE ADJUST
 TITLE BLOCKS ON PLANS ACCORDINGLY.
 FBC 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON PLANS AS WELL AS ON ELECTRICAL PLANS. SOME CODES
 REFERENCE ON PLANS ARE NO LONGER ADOPTED BY THE STATE
 OF FLORIDA AND HAVE NOT BEEN FOR SEVERAL YEARS. PLEASE
 SEE COVER SHEET FOR EXAMPLE WHICH STATES THE *STANDARD
 BUILDING CODE*. SBC. THE FOLLOWING SHALL BE LISTED AT A
 MINIMUM FOR THIS REVIEWER AND FOR THIS TRADE.
  
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 3) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR, MATERIALS, DESIGN COST,
 EQUIPMENT ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THE APPLIED TOTAL VALUE OF $19K IS LOW FOR
 SCOPE OF WORK, EQUIPMENT ETC AS SHOWN ON PLANS.
 FBC 108.3
  
 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR
 NEW PROPOSED EQUIPMENT. MUST CONTAIN A LISTING FROM A
 NRTL. (NATIONALLY RECOGNIZED TESTING LABORATORY).
 110.3,90.7
  
 5) NOTE: ELECTRICAL PLAN SHEET E-1 MENTIONS A NEW METER
 AND MAIN. HOWEVER BY THE RISER THIS IS NOT A NEW MAIN
 AND IS IN FACT A TENANT MEANS OF DISCONNECT. THIS IS
 NOT A MAIN FOR THE SERVICE FEEDING TENANTS. PLEASE
 ADJUST DESIGNATIONS AND LABELING OF EQUIPMENT.
 230.2E
 THIS IS ALL ONE TENANT SPACE YET THE RISER MENTIONS A
 NEW METER AND MAIN FOR TENANT SUITE/UNIT 1723. A NEW
 MAIN FOR THE SAME TENANT IS NOT GRANTED AT THIS TIME.
 NEED TO PROVIDE LOAD ON EXISTING MAIN WITH NEW LOAD
 ADDED IN WHICH NEW 400 TENANT MAIN IS BEING ADDED.
 220.87
 PLEASE BE SURE TO SHOW ANY CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%. 215.3,230.42 ETC
 RISER SHOWS ALL EXISTING AND NEW TENANT MAINS AS
 SEPARATE SUITES OR UNIT HOWEVER BASED ON THE PLANS
 SUBMITTED THIS IS NOW GOING TO BE ONE TENANT SPACE.
  
 6) NOTE: PLEASE SEE 250.110,250.24, 250.6, 250.122 ETC.
 THE RISER IS MISSING THE EQUIPMENT GROUNDING CONDUCTOR
 AFTER THE FIRST MEANS OF SERVICE DISCONNECT.
 PLEASE ALSO KNOW ANY METERING EQUIPMENT AFTER THE FIRST
 MEANS OF SERVICE EQUIPMENT DISCONNECT REQUIRES A
 FLOATING NEUTRAL IN METER.
  
 7) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL HVE TO THE TRANSFORMER.
 250.20,250.30,250.110,250.122 ETC
  
 8) NOTE: PLEASE SEE THE TRANSFORMER NEEDS TO SHOW THE
 ATTACHMENT LOCATION PER 250.50,250.30,250.20.
  
 9) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS DO NOT
 MATCH THE ON-LINE WEBSITE FROM DBPR. PLEASE ADJUST.
 FAC 61G15-23.002
  
 10) NOTE: ** PLEASE SEE THE COLOR CODING SHALL MATCH
 EXISTING IN THE BUILD FOR 277/480V SYSTEMS. THE NOTES
 ON E-3 NEED TO BE ADJUSTED TO READ BROWN, PURPLE, AND
 YELLOW. ORANGE IS THE COLOR BY THE NEC WHICH IS SET
 ASIDE FOR DELTA HIGH LEG SYSTEMS. THIS IS NOT SUCH A
 SYSTEM.
 PLEASE REVISE TO MATCH EXISTING.
 90.4
 * CALL FOR QUESTIONS
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II