| Plan Review Notes For Permit 08100220 |
| Permit Number |
08100220 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-01-15 15:53:49 | | | | | | | PROVISO | | | | | | THE 200 AMP PANEL "A", IS NOT RATED FOR THE 266 AMP | | | LOAD IN THE CALCULATIONS. A 150 AMP DISCONNECT MUST BE | | | ADDED OUTSIDE AT THE METER. 230230.70(A)(1) |
|