2008-10-28 16:58:03PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET E-2 SANITARY ISOMETRIC: PLEASE CORRECT THE
 FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} THE CLEANOUTS BEING INDICATED FOR THE SECOND FLOOR
 ARE BEING INDICATED IN THE WRONG PLACE. THOSE CLEANOUTS
 SHOULD BE CORRECTLY LOCATED AT THE BASE OF THOSE SOIL
 AND WASTE STACKS ON THE FIRST FLOOR. PLEASE CORRECT PER
 SECTION 708.3.4 BASE OF STACK.
  
 B} THE ISOMETRIC DOES NOT REFLECT THE FIRST FLOOR PLAN
 INDICATED ON SHEET A-3. THE WATER CLOSET IS MISSING
 FROM THE FIRST FLOOR BATHROOM (ROOM NOT NUMBERED) BY
 BEDROOM 3 AND BEDROOM 4. PLEASE KNOW THAT THE ISOMETRIC
 IS INDICATING THREE LAVATORIES FOR THIS BATHROOM,
 HOWEVER THE FIRST FLOOR PLAN ON SHEET A-3 ONLY
 INDICATES TWO LAVATORIES. PLEASE CORRECT PER SECTION
 106.1.1 (W.P.B. AS AMENDED) INFORMATION ON CONSTRUCTION
 DOCUMENTS AND SECTION 701.1 SCOPE.
  
 C} THE ISOMETRIC DOES NOT REFLECT THE FIRST FLOOR PLAN
 INDICATED ON SHEET A-3. THE ISOMETRIC SHOULD CLEARLY
 INDICATE THE REQUIRED BRANCH COMBINATION WYE AND EIGHTH
 BEND FITTING FROM THE MAIN TO THE POWDER ROOM BATHROOM.
 PLEASE KNOW AT A MINIMUM THE SANITARY ISOMETRIC RISER
 DIAGRAM SHOULD REFLECT THE FLOOR PLAN. PLEASE CORRECT
 PER SECTION 106.1.1 (W.P.B. AS AMENDED) INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION 701.1 SCOPE.
  
 D} THE SECOND FLOOR BATHTUB IN THE TUB BATHROOM (ROOM
 NOT NUMBERED) IS NOT VENTED. THE BATHTUB WASTE BRANCH
 FITTING SHOULD BE LOCATED ABOVE THE WATERCLOSET AND
 BELOW THE LAVATORY TO BE VENTED. PLEASE CORRECT PER
 SECTION 901.2.1 VENTING REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  