| 2008-10-28 16:58:03 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET E-2 SANITARY ISOMETRIC: PLEASE CORRECT THE |
| | FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} THE CLEANOUTS BEING INDICATED FOR THE SECOND FLOOR |
| | ARE BEING INDICATED IN THE WRONG PLACE. THOSE CLEANOUTS |
| | SHOULD BE CORRECTLY LOCATED AT THE BASE OF THOSE SOIL |
| | AND WASTE STACKS ON THE FIRST FLOOR. PLEASE CORRECT PER |
| | SECTION 708.3.4 BASE OF STACK. |
| | |
| | B} THE ISOMETRIC DOES NOT REFLECT THE FIRST FLOOR PLAN |
| | INDICATED ON SHEET A-3. THE WATER CLOSET IS MISSING |
| | FROM THE FIRST FLOOR BATHROOM (ROOM NOT NUMBERED) BY |
| | BEDROOM 3 AND BEDROOM 4. PLEASE KNOW THAT THE ISOMETRIC |
| | IS INDICATING THREE LAVATORIES FOR THIS BATHROOM, |
| | HOWEVER THE FIRST FLOOR PLAN ON SHEET A-3 ONLY |
| | INDICATES TWO LAVATORIES. PLEASE CORRECT PER SECTION |
| | 106.1.1 (W.P.B. AS AMENDED) INFORMATION ON CONSTRUCTION |
| | DOCUMENTS AND SECTION 701.1 SCOPE. |
| | |
| | C} THE ISOMETRIC DOES NOT REFLECT THE FIRST FLOOR PLAN |
| | INDICATED ON SHEET A-3. THE ISOMETRIC SHOULD CLEARLY |
| | INDICATE THE REQUIRED BRANCH COMBINATION WYE AND EIGHTH |
| | BEND FITTING FROM THE MAIN TO THE POWDER ROOM BATHROOM. |
| | PLEASE KNOW AT A MINIMUM THE SANITARY ISOMETRIC RISER |
| | DIAGRAM SHOULD REFLECT THE FLOOR PLAN. PLEASE CORRECT |
| | PER SECTION 106.1.1 (W.P.B. AS AMENDED) INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND SECTION 701.1 SCOPE. |
| | |
| | D} THE SECOND FLOOR BATHTUB IN THE TUB BATHROOM (ROOM |
| | NOT NUMBERED) IS NOT VENTED. THE BATHTUB WASTE BRANCH |
| | FITTING SHOULD BE LOCATED ABOVE THE WATERCLOSET AND |
| | BELOW THE LAVATORY TO BE VENTED. PLEASE CORRECT PER |
| | SECTION 901.2.1 VENTING REQUIRED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |