| Date |
Text |
| 2008-10-23 12:02:31 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET E-2, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} THE FEED FOR PANEL "B"IS SHOWN AS #6 CU WHICH IS |
| | RATED FOR AN OCP OF 65 AMPS.(310.16) THE CALCULATION |
| | FOR THAT PANEL INDICATE 141 AMPS. THE FEEDER ON THAT |
| | PANEL IS LISTED AS A 200 AMP. PLEASE CORRELATE. NOTE: |
| | THE AHU'S ALONE ARE ON 60 AMP CIRCUITS. |
| | |
| | 2} THERE IS A WATER HEATER IN THE CALCULATION FOR PANEL |
| | "B" BUT NONE ON THE PANEL SCHEDULE. NOTE THERE IS ALSO |
| | A WATER HEATER IN PANEL "A", BUT ONLY ONE SHOWN ON THE |
| | FLOOR PLANS @ 100 GAL.408.4 |
| | |
| | 3} THE FEED FOR PANEL "B" IS LISTED BOTH AS MAIN LUG |
| | ONLY AND 200 AMP MAIN BREAKER? |
| | |
| | THE FOLLOWING COMMENTS REFER TO SHEET E-1: |
| | |
| | 4} THERE ARE THREE A/C SYSTEMS IN THE LOAD CALCULATIONS |
| | BUT ONLY TWO CONDENSING UNITS LOCATED ON THE PLAN. SHOW |
| | THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. ALSO |
| | SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). |
| | |
| | 5} 210.52 (C)(2) ISLAND COUNTER SPACES AT LEAST ONE |
| | RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER |
| | SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR |
| | GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| | GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN |
| | ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE |
| | RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE |
| | RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND |
| | INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN |
| | 210.52(C)(4). |
| | |
| | 6} 210.52(C)(3) PENINSULAR COUNTER SPACES AT LEAST ONE |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR |
| | COUNTER SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) |
| | OR GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| | GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE |
| | CONNECTING EDGE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |
| | |
| | |