| 2008-10-23 10:22:42 | 2004 FBC W/2007 REVISIONS |
| | TWO STORY ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |
| | 2) ON SHEET A-1 PLEASE ADD ADDITION TO THE SCOPE OF |
| | WORK AND REVISE GENERAL NOTE 1 TO 2004 FBC WITH 2007 |
| | REVISIONS. FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 3) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| | ADDITION AS REQUIRED BY FBC 13-600. THE PREPARER AND |
| | OWNER/AGENT SIGNATURES ARE REQUIRED ON THE FORMS. |
| | |
| | 4) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS . IN |
| | BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| | GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS |
| | THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND |
| | SHALL BE LOCATED IN A HALLWAY OR OTHER READILY |
| | ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM |
| | UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE |
| | SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE |
| | MECHANICAL EQUIPMENT IS LOCATED IN ATTICS. |
| | |
| | 5) SPECIFY HOW THE SECOND FLOOR BALCONY FLOOR WILL BE |
| | WATERPROOFED TO PREVENT WATER INTRUSION INTO THE ROOMS |
| | BELOW. |
| | |
| | 6) SPECIFY THE LOCATIONS OF THE FLOOR/CEILING ASSEMBLY |
| | DRAFTSTOPPING ON THE PLANS. FBC R502.1.2 |
| | |
| | 7) PLEASE CORRECT THE TYPO ON THE LEDGER 1 DETAIL ON |
| | S-2 FROM 58" DIAMETER ANCHOR BOLTS TO 5/8". |
| | |
| | 8) PROVIDE STRUCTURAL DETAILS OF THE SECOND FLOOR ROOF |
| | AREA FOR THE LARGE OVERHANG AT THE CORNER OF THE MASTER |
| | BATHROOM ABOVE THE ANGLE WALL. R801.2 REQUIREMENTS. |
| | ROOF AND CEILING CONSTRUCTION SHALL BE CAPABLE OF |
| | ACCOMMODATING ALL LOADS IMPOSED ACCORDING TO SECTION |
| | R301 AND OF TRANSMITTING THE RESULTING LOADS TO THE |
| | SUPPORTING STRUCTURAL ELEMENTS. |
| | |
| | 9) PROVIDE STRUCTURAL DETAILS OF THE EXISTING ROOF |
| | FRAMING AT THE AREA WHERE THE NEW FLOOR GIRDERS |
| | SUPPORTED BY THE STEEL COLUMN WILL BE INSTALLED BELOW |
| | THE NEW MASTER BATH. R801.2 |
| | |
| | 10) PROVIDE A ROOF FRAMING PLAN AND DETAILS FOR THE |
| | ROOF CRICKETS THAT WILL BE REQUIRED TO DIVERT THE RAIN |
| | WATER AWAY FROM THE SECOND FLOOR WALLS OF THE ADDITION. |
| | R703.1 |
| | |
| | 11) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | GLASS BLOCK, EXTERIOR FRENCH DOORS AND STRUCTURAL |
| | WINDOW MULLIONS AS REQUIRED BY FAC RULE 9B-72. NOTE: IF |
| | PRODUCTS ARE NOT LARGE MISSILE IMPACT RATED, THEN |
| | PRODUCT APPROVALS, INSTALLATION SCHEDULES AND KEY PLANS |
| | FOR STORM PANELS WILL BE REQUIRED. FBC R301.2.1.2 |
| | |
| | 13) SHOP DRAWINGS FOR THE EXTERIOR BALCONY WILL BE |
| | REQUIRED TO BE SUBMITTED FOR APPROVAL BEFORE THEY ARE |
| | INSTALLED. FBC 106.1.2* CITY AMENDMENTS |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |