| Notes |
| Date |
Text |
| 2008-12-02 15:47:33 | *** PROVISO/REDLINED PLANS***** | | | | | | 1) NOTE: CLOSET AREAS WHERE PANELS ARE LOCATED SHALL | | | CONTAIN SIGNAGE ON DOORS WHICH STATES. * ELECTRICAL | | | EQUIPMENT/ROOM* *NO STORAGE*, OR WORDS TO THAT AFFECT. | | | THE LETTERING SHALL BE PART OF PERMANENT SIGN WITH A | | | MINIMUM OF 1 INCH LETTERING ON CONTRASTING BACKGROUND. | | | 408.17, 240.24D, 110.26 | | | | | | 2) NOTE: SINCE SPECIFIC FIXTURES WITH RESPECT TO MODEL | | | NUMBER BRAND ETC WAS NOT PROVIDED AND ONLY MAXIMUM VA | | | THEN PLANS WILL NEED TO BE REVISED WITH ACTUAL FIXTURE | | | AT A LATER DATE. THE MAXIMUM VA STILL SHALL MEET DESIGN | | | VA OF 75WATTS OR LESS. 13-415.2.ABC.1.1, .1.2. | | | | | | | | | ** SUITE/UNIT NUMBER WAS ADDED TO EACH SHEET. ONLY THE | | | MAIN ADDRESS WAS DONE. | | | | | | |
|