2008-12-02 15:47:33*** PROVISO/REDLINED PLANS*****
  
 1) NOTE: CLOSET AREAS WHERE PANELS ARE LOCATED SHALL
 CONTAIN SIGNAGE ON DOORS WHICH STATES. * ELECTRICAL
 EQUIPMENT/ROOM* *NO STORAGE*, OR WORDS TO THAT AFFECT.
 THE LETTERING SHALL BE PART OF PERMANENT SIGN WITH A
 MINIMUM OF 1 INCH LETTERING ON CONTRASTING BACKGROUND.
 408.17, 240.24D, 110.26
  
 2) NOTE: SINCE SPECIFIC FIXTURES WITH RESPECT TO MODEL
 NUMBER BRAND ETC WAS NOT PROVIDED AND ONLY MAXIMUM VA
 THEN PLANS WILL NEED TO BE REVISED WITH ACTUAL FIXTURE
 AT A LATER DATE. THE MAXIMUM VA STILL SHALL MEET DESIGN
 VA OF 75WATTS OR LESS. 13-415.2.ABC.1.1, .1.2.
  
  
 ** SUITE/UNIT NUMBER WAS ADDED TO EACH SHEET. ONLY THE
 MAIN ADDRESS WAS DONE.
  
  