| 2008-10-16 09:23:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. USE OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL |
| | BUILDINGS IS TO BE APPROVED BY THE BUILDING OFFICIAL |
| | THROUGH A PRESTORM PREPARATION PLAN; SEE WIND-BORNE |
| | DEBRIS IMPLEMENTATION STANDARD, ITEM 13. IMPACT ON THE |
| | SECOND FLOOR IS GENERALLY REQUIRED. HTTP://WWW.CITYOFWP |
| | B.COM/CONSTRUCTION/PDF/WIND-BORNE_DEBRIS_IMPLEMETATION. |
| | PDF |
| | |
| | THIS DOCUMENT IS ALSO AVAILABLE IN THE LOBBY OF |
| | CONSTRUCTION SERVICES. |
| | |
| | 2. IF USE OF REMOVABLE STORM PANELS IS APPROVED, AN |
| | INSTALLATION SCHEDULE IS REQUIRED TO DEMONSTRATE |
| | COMPLIANCE WITH FBC R301 (WIND). TWO SETS REQUIRED. HTT |
| | P://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INS |
| | TALLATION.PDF |
| | |
| | 3. THE ELECTRIC PERMIT 07010976 FOR THIS PROPERTY (AND |
| | ASSOCIATED WITH WORK FOR THIS PERMIT), IS EXPIRED. |
| | PLEASE ADVISE AS TO STATUS. NOTE THAT THIS IS AN |
| | APPLICATION TO REPAIR SHEETROCK ASSOCIATED WITH THE |
| | ELECTRIC PERMIT. |
| | |
| | 4. THE PERMIT APPLICATION SCOPE INCLUDES REPAIR OF A |
| | STAIRWAY. PROVIDE A STRUCTURAL DETAIL AND SITE PLAN |
| | WHICH CLEARLY SHOWS SCOPE, LOCATION, AND METHOD OF |
| | REPAIR, FBC*106, FBC R301. |
| | |
| | 5. DECLARE GOVERNING CODE, INCLUDING 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 6. DECLARE WIND DESIGN CRITERIA, FBC R301. |
| | |
| | 7. DECLARE LEVEL OF ALTERATION FBC EB 301.5. |
| | |
| | 8. STRUCTURAL DETAILS PREPARED BY AN ENGINEER WERE |
| | SUBMITTED. THIS IS NOT INCLUDED IN THE SCOPE OF WORK ON |
| | THE APPLICATION. IT IS NOT CLEAR WHY THESE DETAILS HAVE |
| | BEEN PROVIDED. THE DETAIL STATES THAT THE 2X4 IS "AS |
| | NEEDED FOR REINFOCEMENT". REINFORCEMENT - STRUCTURAL |
| | FOR THE WALL, OR BLOCKING FOR THE DRYWALL? THE |
| | APPLICATION STATES "REPAIR SHEETROCK FOR UPDATED |
| | ELECTRICAL". CLARIFY EXTENT OF DRYWALL REPAIR. |
| | |
| | 9. INSULATION IS NOT SHOWN, WALL AND TENANT SEPARATION |
| | (FLOOR/CEILING), FBC13. AS SCOPE IS NOT CLEAR, |
| | COMPLIANCE AND REQUIREMENTS NOT CLEAR AT THIS TIME. |
| | |
| | |
| | |
| | |
| | |