Plan Review Notes
Plan Review Notes For Permit 08100146
Permit Number 08100146
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-21 15:35:20 
 ** DENIED REVIEW**
  
  
  
  
 1) NOTE: PLANS REFLECT NOTES FOR DECK BONDING QUOTING
 FBC 2004104.2.3 FOR ALTERNATE METHODS AND MATERIALS.
 THIS IS INCORRECT. THE PLANS NEED TO CONTAIN A DESIGN
 AND ANY NOTES FROM THE 2005 NFPA-70. ( NEC).
 CHAPTER 1 OF THE FLORIDA BUILDING CODE IS
 ADMINISTRATIVE AS ADOPTED BY EACH JURISDICTION. THIS
 SECTION AS NOTED ON PLANS IS NOT VALID WITH THE CITY OF
 WEST PALM BEACH AS AN ADOPTED SECTION FOR THIS SAME
 NOTE.
 THE FACT REMAINS ALL DESIGN FOR THE EQUAL-POTENTIAL
 BONDING GRID SHALL BE PER THE NEC AS NOTED ABOVE.
  
 2) NOTE: PLEASE ONLY INCLUDE ELECTRICAL FOR THE POOL
 SCOPE OF WORK AS APPLIED. THE PLANS INDICATE LIGHTING
 ETC.
  
 3) NOTE: PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN
 AT 125%.
 230.42,215.3 ETC
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  