| 2008-10-21 15:35:20 | |
| | ** DENIED REVIEW** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLANS REFLECT NOTES FOR DECK BONDING QUOTING |
| | FBC 2004104.2.3 FOR ALTERNATE METHODS AND MATERIALS. |
| | THIS IS INCORRECT. THE PLANS NEED TO CONTAIN A DESIGN |
| | AND ANY NOTES FROM THE 2005 NFPA-70. ( NEC). |
| | CHAPTER 1 OF THE FLORIDA BUILDING CODE IS |
| | ADMINISTRATIVE AS ADOPTED BY EACH JURISDICTION. THIS |
| | SECTION AS NOTED ON PLANS IS NOT VALID WITH THE CITY OF |
| | WEST PALM BEACH AS AN ADOPTED SECTION FOR THIS SAME |
| | NOTE. |
| | THE FACT REMAINS ALL DESIGN FOR THE EQUAL-POTENTIAL |
| | BONDING GRID SHALL BE PER THE NEC AS NOTED ABOVE. |
| | |
| | 2) NOTE: PLEASE ONLY INCLUDE ELECTRICAL FOR THE POOL |
| | SCOPE OF WORK AS APPLIED. THE PLANS INDICATE LIGHTING |
| | ETC. |
| | |
| | 3) NOTE: PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN |
| | AT 125%. |
| | 230.42,215.3 ETC |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |