| 2008-10-22 16:58:57 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A01 IS INDICATING THE WRONG CODE CYCLE OF |
| | FBC-2004 WITH 2006 AMENDMENTS. PLEASE KNOW THAT THE |
| | CORRECT CODE CYCLE IS FBC-2004 WITH 2007 REVISIONS. PER |
| | FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.5 |
| | RECORD RETENTION. |
| | |
| | 2. PLEASE INCLUDE THE ADDRESS ON ALL PLAN SHEETS. PER |
| | FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 3. ENERGY CALCULATIONS NEED TO BE SIGNED BY |
| | OWNER/AGENT. PER FBC-2003 CHAPTER 13, SECTION 13-103.3 |
| | BUILDING PERMITS. |
| | |
| | 4. SHEET A04 PLUMBING RISER: THE FOLLOWING ITEMS NEED |
| | TO BE CORRECTED PER THE FBC-2004 PLUMBING CODE |
| | SECTIONS. |
| | |
| | A} BATH 2: THE BATHTUB IS NOT VENTED. PLEASE REVISE PER |
| | THE RED LINE CORRECTIONS. PER SECTION 901.2.1 VENTING |
| | REQUIRED. |
| | |
| | B} PLEASE LOCATE THE REQUIRED CLEANOUT FOR THE WASHING |
| | MACHINE TO BE LOCATED AT FOUR FEET ABOVE FINNISH FLOOR |
| | (4' A.F.F.) FOR ACCESS. PER SECTION 708.9 ACCESS. |
| | |
| | C} CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE |
| | WASHING MACHINE DRAIN ABOVE THE TRAP WEIR. PER SECTION |
| | 406.3 WASTE CONNECTIONS. |
| | |
| | D} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER AS BEING A TWO-WAY |
| | CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |