2008-10-22 16:58:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A01 IS INDICATING THE WRONG CODE CYCLE OF
 FBC-2004 WITH 2006 AMENDMENTS. PLEASE KNOW THAT THE
 CORRECT CODE CYCLE IS FBC-2004 WITH 2007 REVISIONS. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.5
 RECORD RETENTION.
  
 2. PLEASE INCLUDE THE ADDRESS ON ALL PLAN SHEETS. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3. ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT. PER FBC-2003 CHAPTER 13, SECTION 13-103.3
 BUILDING PERMITS.
  
 4. SHEET A04 PLUMBING RISER: THE FOLLOWING ITEMS NEED
 TO BE CORRECTED PER THE FBC-2004 PLUMBING CODE
 SECTIONS.
  
 A} BATH 2: THE BATHTUB IS NOT VENTED. PLEASE REVISE PER
 THE RED LINE CORRECTIONS. PER SECTION 901.2.1 VENTING
 REQUIRED.
  
 B} PLEASE LOCATE THE REQUIRED CLEANOUT FOR THE WASHING
 MACHINE TO BE LOCATED AT FOUR FEET ABOVE FINNISH FLOOR
 (4' A.F.F.) FOR ACCESS. PER SECTION 708.9 ACCESS.
  
 C} CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE
 WASHING MACHINE DRAIN ABOVE THE TRAP WEIR. PER SECTION
 406.3 WASTE CONNECTIONS.
  
 D} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER AS BEING A TWO-WAY
 CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  