| Plan Review Notes For Permit 08100137 |
| Permit Number |
08100137 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-08 12:08:57 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) ONLY ONE PAGE OF THE COOLING LOAD CALCULATIONS WAS | | | SUBMITTED FOR REVIEW, SUBMIT ALL OF THE COOLING LOAD | | | CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 3) THE MECHANICAL PLAN SHOWS THE CONDENSER UNIT IN A | | | DIFFERENT LOCATION THAN THE BUILDING AND ELECTRICAL | | | PLAN, PLEASE CORRECT. | | | | | | 4) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C | | | CONDENSER UNIT, PER 2004 FBC/R R303.4.2. PLEASE CORRECT | | | BUILDING, ELECTRICAL AND MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|