2008-10-08 12:08:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ONLY ONE PAGE OF THE COOLING LOAD CALCULATIONS WAS
 SUBMITTED FOR REVIEW, SUBMIT ALL OF THE COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) THE MECHANICAL PLAN SHOWS THE CONDENSER UNIT IN A
 DIFFERENT LOCATION THAN THE BUILDING AND ELECTRICAL
 PLAN, PLEASE CORRECT.
  
 4) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C
 CONDENSER UNIT, PER 2004 FBC/R R303.4.2. PLEASE CORRECT
 BUILDING, ELECTRICAL AND MECHANICAL PLANS.
  