Text |
| 2008-10-08 10:31:16 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | ALL COMMENTS RELATE TO SHEET A09, UNLESS OTHERWISE |
| | NOTED. |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. SEE ABOVE. |
| | |
| | 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE |
| | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. |
| | |
| | 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 4} PROVIDE A PANEL SCHEDULE SO THAT BRANCH/FEEDER |
| | CIRCUIT CONDUCTOR AND OVER CURRENT PROTECTION |
| | COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, 106.3.5.4 FBC |
| | AS AMENDED. |
| | |
| | 5} LOCATE THE DISCONNECT ON THE PLAN, SEE 230.70(A)(1) |
| | |
| | 6} AN EQUIPMENT GROUNDING CONDUCTOR PER 250.122 IS |
| | REQUIRED FROM THE DISCONNECT TO THE PANEL, NOTE SAME ON |
| | THE RISER. |
| | |
| | NOTE: IT DOES NOT APPEAR THAT THE PANEL LOCATION IN THE |
| | LAUNDRY ROOM WILL HAVE THE REQUIRED CLEARANCE (3') PER |
| | 110.26 WHEN THE DRYER IS SET. PLEASE VERIFY. |
| | |
| | 7} LABEL THE ROOMS AS PER USE ON SHEET A09. 106.1.3 |
| | FBC. |
| | |
| | 8} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| | |
| | 9} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| | DEFICIENCIES. |
| | |
| | 10} A RECEPTACLE IS REQUIRED AT THE BACK OF THE |
| | DWELLING PER 210.52(E). |
| | |
| | 11} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT OUTLET |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| | SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING MEANS. |
| | |
| | 12} 9B-3.0472 CARBON MONOXIDE PROTECTION. |
| | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW |
| | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON |
| | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM |
| | USED FOR SLEEPING PURPOSES. |
| | (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR |
| | PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING |
| | IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS |
| | SHALL HAVE BATTERY BACK UP. |
| | (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED |
| | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. |
| | HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN. |
| | NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE. |
| | |
| | LOCATE DETECTORS ON THE PLAN IF APPLICABLE. NOTE: MAY |
| | BE COMBINATION SMOKE/CARBON MONOXIDE |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |