| 2008-10-24 16:28:13 | 2004 FBC W/2007 REVISIONS |
| | SFD |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |
| | 3) ON SHEET A01 AND SEVERAL OTHER SHEETS THE 2006 |
| | AMENDMENTS TO THE 2004 IS SPECIFIED. PLEASE UPDATE TO |
| | THE 2007 AMENDMENTS. |
| | |
| | 4) THE TYPE OF CONSTRUCTION ON A02 IS INCORRECT. UNDER |
| | THE 2004 FBC THIS CONSTRUCTION IS TYPE VB. PLEASE |
| | CORRECT. SEE FBC TABLE 601. |
| | |
| | 5) ON SHEET A02, PLEASE SPECIFY THE 2002 EDITIONS OF |
| | THE FOLLOWING STANDARDS AS LISTED IN CHAPTER 43 OF THE |
| | 2004 FBC RESIDENTIAL. ACI 318-02, ACI 301-02 AND ASCE |
| | 5-02. |
| | |
| | 6) SPECIFY THE REQUIRED NUMBER AND SPACING OF THE |
| | SOFFIT VENTS ON A07. SHOW COMPLIANCE WITH FBC R806.2 |
| | MINIMUM AREA. |
| | |
| | 7) ON SHEET A08, PLEASE REVISE THE ROOF SHEATHING |
| | FASTENERS TO 8D RING SHANK NAILS AS REQUIRED BY FBC |
| | R803.2.3.1. |
| | |
| | 8) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY CALCULATION FORMS. FBC 13-600 |
| | |
| | 9) THE TRUSS ENGINEER'S ORIGINAL WET SIGNATURE IS |
| | REQUIRED ON THE TRUSS LAYOUT AND TRUSS DRAWING INDEX |
| | COVER SHEET. FS471 AND FAC 61G15-23.002 |
| | |
| | 10) SUBMIT TWO COPIES OF A SURVEY SPECIFYING THE |
| | LOCATION OF THE STRUCTURE FROM PROPERTY LINES, |
| | EASEMENTS, ETC. FBC R 302.1 |
| | |